The following tables list the default settings for building types in Revit. You can change the default values for many of the building type parameters. See Default Building Type and Space Type Parameters.
Parameter | Default Value |
---|---|
Occupancy Schedule | Warehouse 7 am - 4 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 15 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 0.90 |
Equipment Load Density (W/sq. ft.) | 1.50 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated |
OA L/S Person | N/A |
OA Flow Per Area (cu. M./hr/sq. M.) | 27.4 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 25 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.20 |
Equipment Load Density (W/sq. ft.) | 1.40 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 3.5 |
People Activity Level | Moderately Active Office Work |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.20 |
Equipment Load Density (W/sq. ft.) | 1.40 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Restaurant Lunch and Dinner |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 35 |
People Activity Level | Sedentary Office Work |
People Sensible Heat Gain (W/person) | 81 |
People Latent Heat Gain (W/person) | 81 |
People Sensible Heat Gain (Btu/person) | 275 |
People Latent Heat Gain (Btu/person) | 275 |
Lighting Load Density (W/sq. ft.) | 1.30 |
Equipment Load Density (W/sq. ft.) | 1.50 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 15 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Restaurant Lunch and Dinner |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 50 |
People Activity Level | Sedentary Office Work |
People Sensible Heat Gain (W/person) | 81 |
People Latent Heat Gain (W/person) | 81 |
People Sensible Heat Gain (Btu/person) | 275 |
People Latent Heat Gain (Btu/person) | 275 |
Lighting Load Density (W/sq. ft.) | 1.40 |
Equipment Load Density (W/sq. ft.) | 1.80 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 10 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Restaurant Lunch and Dinner |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 35 |
People Activity Level | Sedentary Office Work |
People Sensible Heat Gain (W/person) | 81 |
People Latent Heat Gain (W/person) | 81 |
People Sensible Heat Gain (Btu/person) | 275 |
People Latent Heat Gain (Btu/person) | 275 |
Lighting Load Density (W/sq. ft.) | 1.60 |
Equipment Load Density (W/sq. ft.) | 1.90 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 10 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Home 24 hours |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 10 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.50 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 7.5 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Retail Facility 7 am - 8 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 10 |
People Activity Level | Walking 3 mph, Light Machine Work |
People Sensible Heat Gain (W/person) | 110 |
People Latent Heat Gain (W/person) | 183 |
People Sensible Heat Gain (Btu/person) | 375 |
People Latent Heat Gain (Btu/person) | 625 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.40 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 10.5 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Health Care Facility 8 am - 9 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 15 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.30 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | School 8 am - 9 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 33.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.10 |
Equipment Load Density (W/sq. ft.) | 1.70 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated |
OA L/S Person | 13 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
Lighting/Equipment Schedule | Offic Lighting 6 am - 11 pm |
People/100 sq. M. | 10 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.20 |
Equipment Load Density (W/sq. ft.) | 1.60 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 10 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Hotel 24 hrs |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 2.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.70 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 9 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Common Office 8 am - 5 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 10 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.30 |
Equipment Load Density (W/sq. ft.) | 1.50 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Warehouse 7 am - 4 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 2.5 |
People Activity Level | Walking 3mph, Light Machine Work |
People Sensible Heat Gain (W/person) | 110 |
People Latent Heat Gain (W/person) | 183 |
People Sensible Heat Gain (Btu/person) | 375 |
People Latent Heat Gain (Btu/person) | 625 |
Lighting Load Density (W/sq. ft.) | 1.30 |
Equipment Load Density (W/sq. ft.) | 2.20 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Hotel 24 hrs |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 2.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 2.00 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 9 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 75 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.20 |
Equipment Load Density (W/sq. ft.) | 1.60 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 9 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Home 24 hrs |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 2.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 0.70 |
Equipment Load Density (W/sq. ft.) | 1.00 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 7.5 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Retail Facility 7 am - 8 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 33.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.10 |
Equipment Load Density (W/sq. ft.) | 1.60 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Common Office 8 am - 5 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 3.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.30 |
Electrical Equipment Radiant Percentage | 0.3 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 10 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Warehouse 7 am - 4 pm |
Lighting/Equipment Schedule | Warehouse Lighting 7 am - 4 pm |
People/100 sq. M. | 2.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 0.30 |
Equipment Load Density (W/sq. ft.) | 0.30 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Vented |
OA L/S Person | N/A |
OA Flow Per Area (cu. M./hr/sq. M.) | 27.4 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Restaurant Lunch and Dinner |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 10 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.20 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated |
OA L/S Person | 9 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 75 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.60 |
Equipment Load Density (W/sq. ft.) | 1.50 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated |
OA L/S Person | 9 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Common Office 8 am - 5 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 15 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.30 |
Electrical Equipment Radiant Percentage | 0.3 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Common Office 8 am - 5 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 3.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.10 |
Equipment Load Density (W/sq. ft.) | 1.60 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 75 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.30 |
Equipment Load Density (W/sq. ft.) | 2.20 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Retail Facility 7 am - 8 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 10 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.50 |
Equipment Load Density (W/sq. ft.) | 1.90 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 7.75 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | School 8 am - 9 pm |
Lighting/Equipment Schedule | School Lighting 7 am - 9 pm |
People/100 sq. M. | 25 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.20 |
Equipment Load Density (W/sq. ft.) | 1.50 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Home 24 hrs |
Lighting/Equipment Schedule | Residential Lighting All Day |
People/100 sq. M. | 0.945 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.00 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 7.5 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 75 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.10 |
Equipment Load Density (W/sq. ft.) | 1.50 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Common Office 8 am - 5 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 33.5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.10 |
Equipment Load Density (W/sq. ft.) | 1.40 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | Y |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
Lighting/Equipment Schedule | Retail Lighting 7 am - 8 pm |
People/100 sq. M. | 50 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 1.00 |
Equipment Load Density (W/sq. ft.) | 1.20 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Warehouse 7 am - 4 pm |
Lighting/Equipment Schedule | Warehouse Lighting 7 am - 4 pm |
People/100 sq. M. | 5 |
People Activity Level | Standing, Light Work, Walking |
People Sensible Heat Gain (W/person) | 73 |
People Latent Heat Gain (W/person) | 59 |
People Sensible Heat Gain (Btu/person) | 250 |
People Latent Heat Gain (Btu/person) | 200 |
Lighting Load Density (W/sq. ft.) | 0.80 |
Equipment Load Density (W/sq. ft.) | 1.20 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated |
OA L/S Person | 6 |
OA Flow Per Area (cu. M./hr/sq. M.) | 0.9 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |
Parameter | Default Value |
---|---|
Occupancy Schedule | Warehouse 7 am - 4 pm |
Lighting/Equipment Schedule | Office Lighting 6 am - 11 pm |
People/100 sq. M. | 10 |
People Activity Level | Light Bench Work |
People Sensible Heat Gain (W/person) | 81 |
People Latent Heat Gain (W/person) | 139 |
People Sensible Heat Gain (Btu/person) | 275 |
People Latent Heat Gain (Btu/person) | 475 |
Lighting Load Density (W/sq. ft.) | 1.40 |
Equipment Load Density (W/sq. ft.) | 1.70 |
Electrical Equipment Radiant Percentage | 0.5 |
Carpet (Y/N) | N |
Condition Type | Heated and Cooled |
OA L/S Person | 8 |
OA Flow Per Area (cu. M./hr/sq. M.) | 3.7 |
Open Time | |
Close Time | |
Unoccupied Cooling Set Point (F) | 82 |