The following tables provide details about the assumptions used during energy analysis for each building type.
These assumptions are based on ASHRAE standards.
Automotive facility
Parameter |
Value |
Occupancy Schedule |
Warehouse
|
People/100 sq. M. |
15 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
9.7 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
NULL |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
27.4 |
Unoccupied Cooling Set Point (C) |
29.4 |
Convention center
Parameter |
Value |
Occupancy Schedule |
Assembly
|
People/100 sq. M. |
25 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
12.9 |
Equipment Load Density (W/sq. M.) |
10.3 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
3.1 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Courthouse
Parameter |
Value |
Occupancy Schedule |
Office
|
People/100 sq. M. |
3.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
12.9 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
2.9 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Dining bar lounge or leisure
Parameter |
Value |
Occupancy Schedule |
Restaurant
|
People/100 sq. M. |
35 |
People Sensible Heat Gain (W/person) |
81 |
People Latent Heat Gain (W/person) |
81 |
Lighting Load Density (W/sq. M.) |
14.0 |
Equipment Load Density (W/sq. M.) |
8.5 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4.7 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Dining cafeteria fast food
Parameter |
Value |
Occupancy Schedule |
Restaurant
|
People/100 sq. M. |
50 |
People Sensible Heat Gain (W/person) |
81 |
People Latent Heat Gain (W/person) |
81 |
Lighting Load Density (W/sq. M.) |
15.1 |
Equipment Load Density (W/sq. M.) |
8.5 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4.7 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Dining family
Parameter |
Value |
Occupancy Schedule |
Restaurant
|
People/100 sq. M. |
35 |
People Sensible Heat Gain (W/person) |
81 |
People Latent Heat Gain (W/person) |
81 |
Lighting Load Density (W/sq. M.) |
17.2 |
Equipment Load Density (W/sq. M.) |
8.5 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
5.1 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Dormitory
Parameter |
Value |
Occupancy Schedule |
Residential
|
People/100 sq. M. |
10 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Exercise center
Parameter |
Value |
Occupancy Schedule |
Retail
|
People/100 sq. M. |
10 |
People Sensible Heat Gain (W/person) |
110 |
People Latent Heat Gain (W/person) |
183 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
10.8 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Fire station
Parameter |
Value |
Occupancy Schedule |
Residential
|
People/100 sq. M. |
3.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
8.5 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Gymnasium
Parameter |
Value |
Occupancy Schedule |
Retail
|
People/100 sq. M. |
33.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
10.8 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
13 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Hospital or healthcare
Parameter |
Value |
Occupancy Schedule |
Health
|
People/100 sq. M. |
10 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
12.9 |
Equipment Load Density (W/sq. M.) |
12.7 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
13 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Hotel
Parameter |
Value |
Occupancy Schedule |
Hotel/Motel
|
People/100 sq. M. |
2.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
5.4 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
5.5 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Library
Parameter |
Value |
Occupancy Schedule |
Office
|
People/100 sq. M. |
10 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
14.0 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
8.5 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Manufacturing
Parameter |
Value |
Occupancy Schedule |
Warehouse
|
People/100 sq. M. |
2.5 |
People Sensible Heat Gain (W/person) |
110 |
People Latent Heat Gain (W/person) |
183 |
Lighting Load Density (W/sq. M.) |
14.0 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
8 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Motel
Parameter |
Value |
Occupancy Schedule |
Hotel/Motel
|
People/100 sq. M. |
2.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
5.4 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
5.5 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Motion picture theatre
Parameter |
Value |
Occupancy Schedule |
Assembly
|
People/100 sq. M. |
75 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
12.9 |
Equipment Load Density (W/sq. M.) |
5.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
2.7 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Multi family
Parameter |
Value |
Occupancy Schedule |
Residential
|
People/100 sq. M. |
2.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
7.5 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
NULL |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
1.1 |
Unoccupied Cooling Set Point (C) |
29.4 |
Museum
Parameter |
Value |
Occupancy Schedule |
Retail
|
People/100 sq. M. |
33.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
11.8 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4.6 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Office
Parameter |
Value |
Occupancy Schedule |
Office
|
People/100 sq. M. |
3.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
14.4 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
8.5 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Parking garage
Parameter |
Value |
Occupancy Schedule |
Warehouse
|
People/100 sq. M. |
2.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
3.2 |
Equipment Load Density (W/sq. M.) |
3.2 |
Infiltration Flow (ACH) |
5 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
NULL |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
27.4 |
Unoccupied Cooling Set Point (C) |
29.4 |
Penitentiary
Parameter |
Value |
Occupancy Schedule |
Residential
|
People/100 sq. M. |
10 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4.9 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Performing arts theatre
Parameter |
Value |
Occupancy Schedule |
Assembly
|
People/100 sq. M. |
75 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
17.2 |
Equipment Load Density (W/sq. M.) |
5.8 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4.9 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Police station
Parameter |
Value |
Occupancy Schedule |
Office
|
People/100 sq. M. |
3.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
5.4 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Post office
Parameter |
Value |
Occupancy Schedule |
Office
|
People/100 sq. M. |
3.5 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
11.8 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4.9 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Religious building
Parameter |
Value |
Occupancy Schedule |
Assembly
|
People/100 sq. M. |
75 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
14.0 |
Equipment Load Density (W/sq. M.) |
10.3 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
8.5 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Retail
Parameter |
Value |
Occupancy Schedule |
Retail
|
People/100 sq. M. |
10 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
16.1 |
Equipment Load Density (W/sq. M.) |
10.1 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
2.8 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
School or university
Parameter |
Value |
Occupancy Schedule |
School
|
People/100 sq. M. |
25 |
People Sensible Heat Gain (W/person) |
73 |
People Latent Heat Gain (W/person) |
59 |
Lighting Load Density (W/sq. M.) |
12.9 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.25 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
7.8 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Single family
Parameter |
Value |
Occupancy Schedule |
Residential
|
People/100 sq. M. |
0.945 |
People Sensible Heat Gain (W/person) |
72 |
People Latent Heat Gain (W/person) |
45 |
Lighting Load Density (W/sq. M.) |
4.8 |
Equipment Load Density (W/sq. M.) |
4.6 |
Infiltration Flow (ACH) |
0.5 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
NULL |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
1.1 |
Unoccupied Cooling Set Point (C) |
29.4 |
Sports arena
Parameter |
Value |
Occupancy Schedule |
Assembly
|
People/100 sq. M. |
75 |
People Sensible Heat Gain (W/person) |
73.3 |
People Latent Heat Gain (W/person) |
58.6 |
Lighting Load Density (W/sq. M.) |
11.8 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
6.7 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Town hall
Parameter |
Value |
Occupancy Schedule |
Office
|
People/100 sq. M. |
33.5 |
People Sensible Heat Gain (W/person) |
73.3 |
People Latent Heat Gain (W/person) |
58.6 |
Lighting Load Density (W/sq. M.) |
11.8 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Transportation
Parameter |
Value |
Occupancy Schedule |
Assembly
|
People/100 sq. M. |
50 |
People Sensible Heat Gain (W/person) |
73.3 |
People Latent Heat Gain (W/person) |
58.6 |
Lighting Load Density (W/sq. M.) |
10.9 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
3.1 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Warehouse
Parameter |
Value |
Occupancy Schedule |
Warehouse
|
People/100 sq. M. |
1.5 |
People Sensible Heat Gain (W/person) |
73.3 |
People Latent Heat Gain (W/person) |
58.6 |
Lighting Load Density (W/sq. M.) |
8.6 |
Equipment Load Density (W/sq. M.) |
4.6 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
4.1 |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
3.7 |
Unoccupied Cooling Set Point (C) |
29.4 |
Workshop
Parameter |
Value |
Occupancy Schedule |
Warehouse
|
People/100 sq. M. |
5 |
People Sensible Heat Gain (W/person) |
81 |
People Latent Heat Gain (W/person) |
139 |
Lighting Load Density (W/sq. M.) |
15.1 |
Equipment Load Density (W/sq. M.) |
10.8 |
Infiltration Flow (ACH) |
0.1 |
Outside Air (ventilation air) Flow Per Person (liters per second) |
NULL |
Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter) |
1.1 |
Unoccupied Cooling Set Point (C) |
29.4 |