You can change the default values for space type parameters. See About Default Building Type and Space Type Parameters.
The following tables list the default settings for space types in Revit.
Active Storage
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Warehouse 7 am - 4 pm |
People/100 sq. M. |
3.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.8 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Active Storage - Hospital/healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
3.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.9 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Air/Train/Bus - Baggage Area
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
100.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Airport Concourse
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
100 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.6 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Atrium - Each additional floor
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
33.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.2 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Atrium - First 3 floors
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
33.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.6 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Audience/Seating Area - Penitentiary
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
150 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.7 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Audience/Seating Area - Exercise Center
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Audience/Seating Area - Gymnasium
Parameter |
Default Value |
Occupancy Schedule |
Common Commercial 7 am - 6 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.4 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Audience/Seating Area - Sports Arena
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.4 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Audience/Seating Area - Convention Center
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
150 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.7 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Audience/Seating Area - Motion Picture Theatre
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
1.2 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Audience/Seating Area - Performing Arts Theatre
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
2.6 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Audience/Seating Area - Religious
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
120 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
1.7 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Audience/Seating Area - Police/Fire Station
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
50.0 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.93 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Audience/Seating Area - Courthouse
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
70.0 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.93 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Audience/Seating Area - Auditorium
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.93 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Bank Customer Area
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
30.0 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
1.49 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Banking Activity Area - Office
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
5.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.5 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.3 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Barber and Beauty Parlor
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
25.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1 |
Power Load Density (W/sq. ft.) |
2 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Card File and Cataloguing - Library
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Classroom/Lecture/Training - Penitentiary
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
65.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Classroom/Lecture/Training
Parameter |
Default Value |
Occupancy Schedule |
School 8 am - 9 pm |
Power Schedule |
School 7 am - 9 pm |
People/100 sq. M. |
65.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.4 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Confinement Cells - Penitentiary
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
25.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.93 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Confinement Cells - Court House
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
25.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.9 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Conference/Meeting/Multipurpose
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
50.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Corridor/Transition
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.5 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Corridor/Transition - Manufacturing Facility
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
00.5 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Corridor w/Patient Waiting Exam - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Court Sports Area - Sports Area
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
30.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.3 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Courtroom - Court House
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
70.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.3 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Department Store Sales - Retail
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
15.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.14 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Detailed - Manufacturing Facility
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.1 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dining Area
Parameter |
Default Value |
Occupancy Schedule |
Restaurant Lunch and Dinner |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
70.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
275 |
Lighting Load Density (W/sq. ft.) |
0.9 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Dining Area - Hotel
Parameter |
Default Value |
Occupancy Schedule |
Restaurant Lunch and Dinner |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
70.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
275 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Dining Area - Family Dining
Parameter |
Default Value |
Occupancy Schedule |
Restaurant Lunch and Dinner |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
70.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
275 |
Lighting Load Density (W/sq. ft.) |
2.1 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Dining Area - Lounge/Leisure Dining
Parameter |
Default Value |
Occupancy Schedule |
Restaurant Lunch and Dinner |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
70.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
275 |
Lighting Load Density (W/sq. ft.) |
1.4 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dining Area - Motel
Parameter |
Default Value |
Occupancy Schedule |
Hotel 24 hrs |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
70.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
275 |
Lighting Load Density (W/sq. ft.) |
1.2 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dining Area - Transportation
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
100.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
275 |
Lighting Load Density (W/sq. ft.) |
0.93 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dining Area - Penitentiary
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
100.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
275 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dining Area - Civil Services
Parameter |
Default Value |
Occupancy Schedule |
Restaurant Lunch and Dinner |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
100.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
275 |
Lighting Load Density (W/sq. ft.) |
0.93 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dormitory Bedroom
Parameter |
Default Value |
Occupancy Schedule |
Home 24 hrs |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
155 |
Lighting Load Density (W/sq. ft.) |
1.11 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Dormitory Study Hall
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
155 |
Lighting Load Density (W/sq. ft.) |
1.11 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Dressing/Locker/Fitting Room - Gymnasium
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.6 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dressing/Locker/Fitting Room - Court House
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Lighting Schedule |
Office Lighting 6 am - 11 pm |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.56 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dressing/Locker/Fitting Room - Performing Arts Theatre
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.56 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dressing/Locker/Fitting Room - Auditorium
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.56 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Dressing/Locker/Fitting Room - Exercise Center
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.56 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Electrical/Mechanical
Parameter |
Default Value |
Occupancy Schedule |
Restaurant Lunch and Dinner |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
3.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.5 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Elevator Lobbies
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
0.2 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Emergency - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.7 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Equipment Room - Manufacturing Facility
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
3.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.2 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Exam/Treatment - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.5 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Exercise Area - Exercise Center
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
30.0 |
People Sensible Heat Gain (Btu/hr) |
710 |
People Latent Heat Gain (Btu/hr) |
1090 |
Lighting Load Density (W/sq. ft.) |
0.93 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Exercise Area - Gymnasium
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
30.0 |
People Sensible Heat Gain (Btu/hr) |
710 |
People Latent Heat Gain (Btu/hr) |
1090 |
Lighting Load Density (W/sq. ft.) |
0.9 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Exhibit Space - Convention Center
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
50.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Fellowship Hall - Religious Buildings
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
120.0 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.9 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Fine Material - Warehouse
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Warehouse 7 am - 4 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.4 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Fine Merchandise - Sales Area Retail
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
15.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.14 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Fire Station Engine Room - Police Fire Station
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.8 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Food Preparation
Parameter |
Default Value |
Occupancy Schedule |
Restaurant Lunch and Dinner |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.2 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Garage Service/Repair - Automotive Facility
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.7 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
General High Bay - Manufacturing Facility
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.7 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
General Low Bay - Manufacturing Facility
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.2 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
General Exhibition - Museum
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
40.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Hospital - Nursery - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.6 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Hospital - Medical Supplies - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
3.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.4 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Hospital/Radiology- Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.4 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Hotel/Conference Center - Conference/Meeting
Parameter |
Default Value |
Occupancy Schedule |
Hotel 24 hrs |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
50.0 |
People Sensible Heat Gain (Btu/hr) |
225 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Inactive Storage
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Warehouse 7 am - 4 pm |
People/100 sq. M. |
3.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.3 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Judges Chambers - Court House
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
50.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Laboratory - Office
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
5.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.4 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Laundry - Ironing and Sorting
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
475 |
Lighting Load Density (W/sq. ft.) |
0.56 |
Power Load Density (W/sq. ft.) |
3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Laundry - Washing - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
275 |
People Latent Heat Gain (Btu/hr) |
475 |
Lighting Load Density (W/sq. ft.) |
0.6 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Library - Audio Visual - Library - Audio Visual
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
25.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Living Quarters - Dormitory
Parameter |
Default Value |
Occupancy Schedule |
Hotel 24 hrs |
Power Schedule |
Residential Lighting All Day |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
155 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Living Quarters - Motel
Parameter |
Default Value |
Occupancy Schedule |
Hotel 24 hrs |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
155 |
Lighting Load Density (W/sq. ft.) |
1.11 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Living Quarters - Hotel
Parameter |
Default Value |
Occupancy Schedule |
Hotel 24 hrs |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
155 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Lobby
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
150.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
155 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Lobby - Religious Building
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Lobby - Motion Picture Theatre
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Lobby - Auditorium
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Lobby - Performing Arts Theatre
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
3.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Lobby - Post Office
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
150.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.3 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Lobby - Hotel
Parameter |
Default Value |
Occupancy Schedule |
Hotel 24 hrs |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
150.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Lounge or Recreation
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
30.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.21 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Mail Concourse Sales Area - Retail
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
40.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.7 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Mass Merchandising Sales Area - Retail
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Warehouse 7 am - 4 pm |
People/100 sq. M. |
15.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.11 |
Power Load Density (W/sq. ft.) |
0.1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Medium/Bulky Material - Warehouse
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Warehouse 7 am - 4 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.9 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Merchandising Sales Area - Retail
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
15.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.14 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Museum and Gallery - Storage
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
5.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.84 |
Power Load Density (W/sq. ft.) |
0.2 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Nurse Station - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.3 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Office - Enclosed
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
5.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.3 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Office - Open Plan
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
5.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.3 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Office - Common Activity Areas - Inactive Storage
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Warehouse 7 am - 4 pm |
People/100 sq. M. |
3.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.28 |
Power Load Density (W/sq. ft.) |
0.2 |
Electrical Equipment Radiant Percentage |
0.3 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Operating Room - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.2 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Other Televised Playing Area - Sports Arena
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
150.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.4 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Parking Area - Attendant Only - Parking Garage
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
5.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.19 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Parking Area - Pedestrian - Parking Garage
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
5.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.2 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Patient Room - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.7 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Personal Services Sales Area - Retail
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
15.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.14 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Pharmacy - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.2 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Physical Therapy - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.9 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Playing Area Gymnasium
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
30.0 |
People Sensible Heat Gain (Btu/hr) |
710 |
People Latent Heat Gain (Btu/hr) |
1090 |
Lighting Load Density (W/sq. ft.) |
1.4 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Plenum
Parameter |
Default Value |
Occupancy Schedule |
Cooling/Heating Off 24 hrs |
Power Schedule |
Cooling/Heating Off 24 hrs |
People/100 sq. M. |
00 |
People Sensible Heat Gain (Btu/hr) |
0 |
People Latent Heat Gain (Btu/hr) |
0 |
Lighting Load Density (W/sq. ft.) |
0 |
Power Load Density (W/sq. ft.) |
0 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0 |
Carpet (Y/N) |
N |
Police Station Laboratory - Police/Fire Stations
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
25.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.39 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Public and Staff Lounge - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
25.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.84 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Reading Area - Library
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.2 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Reception/Waiting - Transportation
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
100.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Reception/Waiting - Motel
Parameter |
Default Value |
Occupancy Schedule |
Hotel 24 hrs |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
30.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Reception/Waiting - Hotel
Parameter |
Default Value |
Occupancy Schedule |
Hotel 24 hrs |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
30.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.1 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Recovery - Hospital/Healthcare
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.8 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Restoration - Museum
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
40.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.7 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Restrooms
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.9 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Ring Sports Area - Sports Arena
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
70.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.7 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Sleeping Quarters - Police/Fire Station
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
105 |
Lighting Load Density (W/sq. ft.) |
0.3 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Sorting Area - Post Office
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
5.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.2 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Specialty Store Sales Area - Retail
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
15.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.14 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Stacks - Library
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.7 |
Power Load Density (W/sq. ft.) |
1.5 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Stairs - Inactive
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.56 |
Power Load Density (W/sq. ft.) |
0.2 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Stairway
Parameter |
Default Value |
Occupancy Schedule |
Common Office 8 am - 5 pm |
Power Schedule |
Office Lighting 6 am - 11 pm |
People/100 sq. M. |
10.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
0.6 |
Power Load Density (W/sq. ft.) |
0.3 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Supermarket Sales Area - Retail
Parameter |
Default Value |
Occupancy Schedule |
Retail Facility 7 am - 8 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
8.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.1 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Terminal - Ticket Counter - Transportation
Parameter |
Default Value |
Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
100.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.5 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |
Workshop - Workshop
Parameter |
Default Value |
Occupancy Schedule |
Warehouse 7 am - 4 pm |
Power Schedule |
Warehouse 7 am - 4 pm |
People/100 sq. M. |
20.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
1.9 |
Power Load Density (W/sq. ft.) |
1 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
N |
Worship - Pulpit Choir - Religious
Parameter |
Default Value |
Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
Power Schedule |
Retail Lighting 7 am - 8 pm |
People/100 sq. M. |
120.0 |
People Sensible Heat Gain (Btu/hr) |
250 |
People Latent Heat Gain (Btu/hr) |
200 |
Lighting Load Density (W/sq. ft.) |
2.4 |
Power Load Density (W/sq. ft.) |
0.54 |
Electrical Equipment Radiant Percentage |
0.5 |
Infiltration Flow (CFM/sq. ft.) |
0.038 |
Carpet (Y/N) |
Y |