Learn about the default settings for space types in Revit.
When using Revit MEP, you can change the default values for space type parameters. See About Default Building Type and Space Type Parameters.
Active Storage
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Warehouse 7 am - 4 pm |
| People/100 sq. M. |
3.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.8 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Active Storage - Hospital/healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
3.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.9 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Air/Train/Bus - Baggage Area
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
100.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Airport Concourse
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
100 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.6 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Atrium - Each additional floor
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
33.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.2 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Atrium - First 3 floors
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
33.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.6 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Audience/Seating Area - Penitentiary
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
150 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.7 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Audience/Seating Area - Exercise Center
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Audience/Seating Area - Gymnasium
| Parameter |
Default Value |
| Occupancy Schedule |
Common Commercial 7 am - 6 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.4 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Audience/Seating Area - Sports Arena
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.4 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Audience/Seating Area - Convention Center
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
150 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.7 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Audience/Seating Area - Motion Picture Theatre
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
1.2 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Audience/Seating Area - Performing Arts Theatre
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
2.6 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Audience/Seating Area - Religious
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
120 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
1.7 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Audience/Seating Area - Police/Fire Station
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
50.0 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.93 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Audience/Seating Area - Courthouse
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
70.0 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.93 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Audience/Seating Area - Auditorium
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.93 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Bank Customer Area
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
30.0 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
1.49 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Banking Activity Area - Office
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
5.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.5 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.3 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Barber and Beauty Parlor
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
25.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1 |
| Power Load Density (W/sq. ft.) |
2 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Card File and Cataloguing - Library
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Classroom/Lecture/Training - Penitentiary
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
65.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Classroom/Lecture/Training
| Parameter |
Default Value |
| Occupancy Schedule |
School 8 am - 9 pm |
| Power Schedule |
School 7 am - 9 pm |
| People/100 sq. M. |
65.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.4 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Confinement Cells - Penitentiary
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
25.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.93 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Confinement Cells - Court House
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
25.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.9 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Conference/Meeting/Multipurpose
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
50.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Corridor/Transition
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.5 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Corridor/Transition - Manufacturing Facility
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
00.5 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Corridor w/Patient Waiting Exam - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Court Sports Area - Sports Area
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
30.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.3 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Courtroom - Court House
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
70.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.3 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Department Store Sales - Retail
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
15.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.14 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Detailed - Manufacturing Facility
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.1 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dining Area
| Parameter |
Default Value |
| Occupancy Schedule |
Restaurant Lunch and Dinner |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
70.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
275 |
| Lighting Load Density (W/sq. ft.) |
0.9 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Dining Area - Hotel
| Parameter |
Default Value |
| Occupancy Schedule |
Restaurant Lunch and Dinner |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
70.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
275 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Dining Area - Family Dining
| Parameter |
Default Value |
| Occupancy Schedule |
Restaurant Lunch and Dinner |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
70.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
275 |
| Lighting Load Density (W/sq. ft.) |
2.1 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Dining Area - Lounge/Leisure Dining
| Parameter |
Default Value |
| Occupancy Schedule |
Restaurant Lunch and Dinner |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
70.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
275 |
| Lighting Load Density (W/sq. ft.) |
1.4 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dining Area - Motel
| Parameter |
Default Value |
| Occupancy Schedule |
Hotel 24 hrs |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
70.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
275 |
| Lighting Load Density (W/sq. ft.) |
1.2 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dining Area - Transportation
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
100.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
275 |
| Lighting Load Density (W/sq. ft.) |
0.93 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dining Area - Penitentiary
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
100.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
275 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dining Area - Civil Services
| Parameter |
Default Value |
| Occupancy Schedule |
Restaurant Lunch and Dinner |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
100.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
275 |
| Lighting Load Density (W/sq. ft.) |
0.93 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dormitory Bedroom
| Parameter |
Default Value |
| Occupancy Schedule |
Home 24 hrs |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
155 |
| Lighting Load Density (W/sq. ft.) |
1.11 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Dormitory Study Hall
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
155 |
| Lighting Load Density (W/sq. ft.) |
1.11 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Dressing/Locker/Fitting Room - Gymnasium
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.6 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dressing/Locker/Fitting Room - Court House
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Lighting Schedule |
Office Lighting 6 am - 11 pm |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.56 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dressing/Locker/Fitting Room - Performing Arts Theatre
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.56 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dressing/Locker/Fitting Room - Auditorium
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.56 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Dressing/Locker/Fitting Room - Exercise Center
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.56 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Electrical/Mechanical
| Parameter |
Default Value |
| Occupancy Schedule |
Restaurant Lunch and Dinner |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
3.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.5 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Elevator Lobbies
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
0.2 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Emergency - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.7 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Equipment Room - Manufacturing Facility
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
3.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.2 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Exam/Treatment - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.5 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Exercise Area - Exercise Center
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
30.0 |
| People Sensible Heat Gain (Btu/hr) |
710 |
| People Latent Heat Gain (Btu/hr) |
1090 |
| Lighting Load Density (W/sq. ft.) |
0.93 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Exercise Area - Gymnasium
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
30.0 |
| People Sensible Heat Gain (Btu/hr) |
710 |
| People Latent Heat Gain (Btu/hr) |
1090 |
| Lighting Load Density (W/sq. ft.) |
0.9 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Exhibit Space - Convention Center
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
50.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Fellowship Hall - Religious Buildings
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
120.0 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.9 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Fine Material - Warehouse
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Warehouse 7 am - 4 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.4 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Fine Merchandise - Sales Area Retail
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
15.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.14 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Fire Station Engine Room - Police Fire Station
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.8 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Food Preparation
| Parameter |
Default Value |
| Occupancy Schedule |
Restaurant Lunch and Dinner |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.2 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Garage Service/Repair - Automotive Facility
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.7 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
General High Bay - Manufacturing Facility
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.7 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
General Low Bay - Manufacturing Facility
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.2 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
General Exhibition - Museum
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
40.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Hospital - Nursery - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.6 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Hospital - Medical Supplies - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
3.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.4 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Hospital/Radiology- Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.4 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Hotel/Conference Center - Conference/Meeting
| Parameter |
Default Value |
| Occupancy Schedule |
Hotel 24 hrs |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
50.0 |
| People Sensible Heat Gain (Btu/hr) |
225 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Inactive Storage
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Warehouse 7 am - 4 pm |
| People/100 sq. M. |
3.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.3 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Judges Chambers - Court House
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
50.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Laboratory - Office
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
5.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.4 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Laundry - Ironing and Sorting
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
475 |
| Lighting Load Density (W/sq. ft.) |
0.56 |
| Power Load Density (W/sq. ft.) |
3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Laundry - Washing - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
275 |
| People Latent Heat Gain (Btu/hr) |
475 |
| Lighting Load Density (W/sq. ft.) |
0.6 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Library - Audio Visual - Library - Audio Visual
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
25.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Living Quarters - Dormitory
| Parameter |
Default Value |
| Occupancy Schedule |
Hotel 24 hrs |
| Power Schedule |
Residential Lighting All Day |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
155 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Living Quarters - Motel
| Parameter |
Default Value |
| Occupancy Schedule |
Hotel 24 hrs |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
155 |
| Lighting Load Density (W/sq. ft.) |
1.11 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Living Quarters - Hotel
| Parameter |
Default Value |
| Occupancy Schedule |
Hotel 24 hrs |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
155 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Lobby
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
150.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
155 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Lobby - Religious Building
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Lobby - Motion Picture Theatre
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Lobby - Auditorium
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Lobby - Performing Arts Theatre
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
3.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Lobby - Post Office
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
150.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.3 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Lobby - Hotel
| Parameter |
Default Value |
| Occupancy Schedule |
Hotel 24 hrs |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
150.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Lounge or Recreation
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
30.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.21 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Mail Concourse Sales Area - Retail
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
40.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.7 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Mass Merchandising Sales Area - Retail
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Warehouse 7 am - 4 pm |
| People/100 sq. M. |
15.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.11 |
| Power Load Density (W/sq. ft.) |
0.1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Medium/Bulky Material - Warehouse
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Warehouse 7 am - 4 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.9 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Merchandising Sales Area - Retail
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
15.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.14 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Museum and Gallery - Storage
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
5.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.84 |
| Power Load Density (W/sq. ft.) |
0.2 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Nurse Station - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.3 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Office - Enclosed
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
5.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.3 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Office - Open Plan
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
5.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.3 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Office - Common Activity Areas - Inactive Storage
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Warehouse 7 am - 4 pm |
| People/100 sq. M. |
3.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.28 |
| Power Load Density (W/sq. ft.) |
0.2 |
| Electrical Equipment Radiant Percentage |
0.3 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Operating Room - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.2 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Other Televised Playing Area - Sports Arena
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
150.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.4 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Parking Area - Attendant Only - Parking Garage
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
5.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.19 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Parking Area - Pedestrian - Parking Garage
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
5.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.2 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Patient Room - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.7 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Personal Services Sales Area - Retail
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
15.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.14 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Pharmacy - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.2 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Physical Therapy - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.9 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Playing Area Gymnasium
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
30.0 |
| People Sensible Heat Gain (Btu/hr) |
710 |
| People Latent Heat Gain (Btu/hr) |
1090 |
| Lighting Load Density (W/sq. ft.) |
1.4 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Plenum
| Parameter |
Default Value |
| Occupancy Schedule |
Cooling/Heating Off 24 hrs |
| Power Schedule |
Cooling/Heating Off 24 hrs |
| People/100 sq. M. |
00 |
| People Sensible Heat Gain (Btu/hr) |
0 |
| People Latent Heat Gain (Btu/hr) |
0 |
| Lighting Load Density (W/sq. ft.) |
0 |
| Power Load Density (W/sq. ft.) |
0 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0 |
| Carpet (Y/N) |
N |
Police Station Laboratory - Police/Fire Stations
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
25.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.39 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Public and Staff Lounge - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
25.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.84 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Reading Area - Library
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.2 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Reception/Waiting - Transportation
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
100.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Reception/Waiting - Motel
| Parameter |
Default Value |
| Occupancy Schedule |
Hotel 24 hrs |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
30.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Reception/Waiting - Hotel
| Parameter |
Default Value |
| Occupancy Schedule |
Hotel 24 hrs |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
30.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.1 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Recovery - Hospital/Healthcare
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.8 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Restoration - Museum
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
40.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.7 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Restrooms
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.9 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Ring Sports Area - Sports Arena
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
70.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.7 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Sleeping Quarters - Police/Fire Station
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
105 |
| Lighting Load Density (W/sq. ft.) |
0.3 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Sorting Area - Post Office
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
5.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.2 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Specialty Store Sales Area - Retail
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
15.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.14 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Stacks - Library
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.7 |
| Power Load Density (W/sq. ft.) |
1.5 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Stairs - Inactive
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.56 |
| Power Load Density (W/sq. ft.) |
0.2 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Stairway
| Parameter |
Default Value |
| Occupancy Schedule |
Common Office 8 am - 5 pm |
| Power Schedule |
Office Lighting 6 am - 11 pm |
| People/100 sq. M. |
10.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
0.6 |
| Power Load Density (W/sq. ft.) |
0.3 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Supermarket Sales Area - Retail
| Parameter |
Default Value |
| Occupancy Schedule |
Retail Facility 7 am - 8 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
8.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.1 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Terminal - Ticket Counter - Transportation
| Parameter |
Default Value |
| Occupancy Schedule |
Healthcare Facility 8 am - 9 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
100.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.5 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |
Workshop - Workshop
| Parameter |
Default Value |
| Occupancy Schedule |
Warehouse 7 am - 4 pm |
| Power Schedule |
Warehouse 7 am - 4 pm |
| People/100 sq. M. |
20.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
1.9 |
| Power Load Density (W/sq. ft.) |
1 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
N |
Worship - Pulpit Choir - Religious
| Parameter |
Default Value |
| Occupancy Schedule |
Large Assembly Hall 8 am - 10 pm |
| Power Schedule |
Retail Lighting 7 am - 8 pm |
| People/100 sq. M. |
120.0 |
| People Sensible Heat Gain (Btu/hr) |
250 |
| People Latent Heat Gain (Btu/hr) |
200 |
| Lighting Load Density (W/sq. ft.) |
2.4 |
| Power Load Density (W/sq. ft.) |
0.54 |
| Electrical Equipment Radiant Percentage |
0.5 |
| Infiltration Flow (CFM/sq. ft.) |
0.038 |
| Carpet (Y/N) |
Y |