Space Type Data for Heating and Cooling Loads Analysis

You can change the default values for many of the space type parameters.

The following tables list the default settings for space types in Revit. See About Default Building Type and Space Type Parameters.

Active Storage

Parameter Default Value
Area per Person (sq. ft.) 358.80
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.80
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Warehouse Lighting - 7 am - 4 pm
Power Schedule Warehouse Lighting - 7 am - 4 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Active Storage - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 358.80
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.90
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Air/Train/Bus - Baggage Area

Parameter Default Value
Area per Person (sq. ft.) 10.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.00
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Airport - Concourse

Parameter Default Value
Area per Person (sq. ft.) 10.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.60
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Atrium - Each Additional Floor

Parameter Default Value
Area per Person (sq. ft.) 32.62
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.20
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Atrium - First Three Floors

Parameter Default Value
Area per Person (sq. ft.) 32.62
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.60
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Penitentiary

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.70
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Exercise Center

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Gymnasium

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.40
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Commercial Occupancy - 7 am - 6 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Sports Arena

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.40
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Convention Center

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.70
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Motion Picture Theatre

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 1.20
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Performing Arts Theatre

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 2.60
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Religious

Parameter Default Value
Area per Person (sq. ft.) 8.97
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 1.70
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy- 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Police/Fire Station

Parameter Default Value
Area per Person (sq. ft.) 21.53
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.93
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Court House

Parameter Default Value
Area per Person (sq. ft.) 15.38
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.93
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Audience/Seating Area - Auditorium

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.93
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Bank Customer Area

Parameter Default Value
Area per Person (sq. ft.) 35.88
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 1.49
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Banking Activity Area - Office

Parameter Default Value
Area per Person (sq. ft.) 215.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.50
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Barber and Beauty Parlor

Parameter Default Value
Area per Person (sq. ft.) 43.06
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.00
Power Load Density (W/sq. ft.) 2.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Card File and Cataloguing - Library

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Classroom/Lecture/Training - Penitentiary

Parameter Default Value
Area per Person (sq. ft.) 16.56
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Classroom/Lecture/Training

Parameter Default Value
Area per Person (sq. ft.) 16.56
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.40
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule School Occupancy - 8 am - 9 pm
Lighting Schedule School Lighting - 7 am - 9 pm
Power Schedule School Lighting - 7 am - 9 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Confinement Cells - Penitentiary

Parameter Default Value
Area per Person (sq. ft.) 43.06
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.93
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Confinement Cells - Court House

Parameter Default Value
Area per Person (sq. ft.) 43.06
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.90
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Conference/Meeting/Multipurpose

Parameter Default Value
Area per Person (sq. ft.) 21.53
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Corridor/Transition

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.50
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Corridor/Transition - Manufacturing Facility

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.50
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Corridors with Patient Waiting Exam - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.00
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Court Sports Area - Sports Area

Parameter Default Value
Area per Person (sq. ft.) 35.88
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.30
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.30
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Courtroom - Courthouse

Parameter Default Value
Area per Person (sq. ft.) 15.38
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.90
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Department Store Sales Area - Retail

Parameter Default Value
Area per Person (sq. ft.) 71.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.14
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Detailed - Manufacturing Facility

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.10
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method

Dining Area

Parameter Default Value
Area per Person (sq. ft.) 15.38
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 80.59
Lighting Load Density (W/sq. ft.) 0.90
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Restaurant Occupancy - Lunch and Dinner
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dining Area - Hotel

Parameter Default Value
Area per Person (sq. ft.) 15.38
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 80.59
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Restaurant Occupancy - Lunch and Dinner
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dining Area - Family Dining

Parameter Default Value
Area per Person (sq. ft.) 15.38
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 80.59
Lighting Load Density (W/sq. ft.) 2.10
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Restaurant Occupancy - Lunch and Dinner
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dining Area - Lounge/Leisure Dining

Parameter Default Value
Area per Person (sq. ft.) 15.38
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 80.59
Lighting Load Density (W/sq. ft.) 1.40
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Restaurant Occupancy - Lunch and Dinner
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dining Area - Motel

Parameter Default Value
Area per Person (sq. ft.) 15.38
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 80.59
Lighting Load Density (W/sq. ft.) 1.20
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Hotel Occupancy - 24 hrs
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dining Area - Transportation

Parameter Default Value
Area per Person (sq. ft.) 10.76
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 80.59
Lighting Load Density (W/sq. ft.) 0.93
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dining Area - Penitentiary

Parameter Default Value
Area per Person (sq. ft.) 10.76
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 80.59
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dining Area - Civil Services

Parameter Default Value
Area per Person (sq. ft.) 10.76
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 80.59
Lighting Load Density (W/sq. ft.) 10.93
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Restaurant Occupancy - Lunch and Dinner
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dormitory Bedroom

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 45.43
Lighting Load Density (W/sq. ft.) 1.11
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Home Occupancy - 24 hrs
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dormitory Study Hall

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 45.43
Lighting Load Density (W/sq. ft.) 1.11
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dressing/Locker/Fitting Room - Gymnasium

Parameter Default Value
Area per Person (sq. ft.) 53.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.60
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dressing/Locker/Fitting Room - Courthouse

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.56
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dressing/Locker/Fitting Room - Performing Arts Theatre

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.56
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dressing/Locker/Fitting Room - Auditorium

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.56
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Dressing/Locker/Fitting Room - Exercise Center

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.56
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Electrical/Mechanical

Parameter Default Value
Area per Person (sq. ft.) 358.80
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.50
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Restaurant Occupancy - Lunch and Dinner
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Elevator Lobbies

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.20
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Emergency - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.70
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Equipment Room - Manufacturing Facility

Parameter Default Value
Area per Person (sq. ft.) 358.80
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.20
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Exam/Treatment - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.50
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Exercise Area - Exercise Center

Parameter Default Value
Area per Person (sq. ft.) 35.88
Sensible Heat Gain per person (W) 208.08
Latent Heat per person (W) 319.45
Lighting Load Density (W/sq. ft.) 0.93
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 20.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Exercise Area - Gymnasium

Parameter Default Value
Area per Person (sq. ft.) 35.88
Sensible Heat Gain per person (W) 208.08
Latent Heat per person (W) 319.45
Lighting Load Density (W/sq. ft.) 0.90
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 20.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Exhibit Space - Convention Center

Parameter Default Value
Area per Person (sq. ft.) 21.53
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Fellowship Hall - Religious Buildings

Parameter Default Value
Area per Person (sq. ft.) 8.97
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.90
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Fine Material - Warehouse

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.40
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Warehouse Lighting - 7 am - 4 pm
Power Schedule Warehouse Lighting - 7 am - 4 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Fine Merchandise - Sales Area Retail

Parameter Default Value
Area per Person (sq. ft.) 71.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.14
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Fire Station Engine Room - Police/Fire Station

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.80
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Food Preparation

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.20
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Restaurant Occupancy - Lunch and Dinner
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Garage Service/Repair - Automotive Facility

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.70
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

General High Bay - Manufacturing Facility

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.70
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

General Low Bay - Manufacturing Facility

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.20
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

General Exhibition - Museum

Parameter Default Value
Area per Person (sq. ft.) 26.91
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.00
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Hospital - Nursery - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.60
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Hospital/Medical Supplies - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 358.80
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.40
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Hospital/Radiology- Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.40
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 3.000000
Outdoor Air Method by People and by Area

Hotel/Conference Center - Conference/Meeting

Parameter Default Value
Area per Person (sq. ft.) 21.53
Sensible Heat Gain per person (W) 65.94
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Hotel Occupancy - 24 hrs
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Inactive Storage

Parameter Default Value
Area per Person (sq. ft.) 358.80
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.30
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Warehouse Lighting - 7 am - 4 pm
Power Schedule Warehouse Lighting - 7 am - 4 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Judges Chambers - Courthouse

Parameter Default Value
Area per Person (sq. ft.) 21.53
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Laboratory - Office

Parameter Default Value
Area per Person (sq. ft.) 215.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.40
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 4.72
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Laundry - Ironing and Sorting

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 139.21
Lighting Load Density (W/sq. ft.) 0.56
Power Load Density (W/sq. ft.) 3.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Laundry - Washing - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 80.59
Latent Heat per person (W) 139.21
Lighting Load Density (W/sq. ft.) 0.60
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Library - Audio Visual - Library - Audio Visual

Parameter Default Value
Area per Person (sq. ft.) 43.06
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Living Quarters - Dormitory

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 45.43
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Hotel Occupancy - 24 hrs
Lighting Schedule Residential Lighting - All Day
Power Schedule Residential Lighting - All Day
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Living Quarters - Motel

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 45.43
Lighting Load Density (W/sq. ft.) 1.11
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Hotel Occupancy - 24 hrs
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Living Quarters - Hotel

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 45.43
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Hotel Occupancy - 24 hrs
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Lobby

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Lobby - Religious Building

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Lobby - Motion Picture Theatre

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Lobby - Auditorium

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Lobby - Performing Arts Theatre

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Lobby - Post Office

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.30
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Lobby - Hotel

Parameter Default Value
Area per Person (sq. ft.) 35.88
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Hotel Occupancy - 24 hrs
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Lounge/Recreation

Parameter Default Value
Area per Person (sq. ft.) 43.06
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.21
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Mail Concourse Sales Area - Retail

Parameter Default Value
Area per Person (sq. ft.) 26.91
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.70
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Mass Merchandising Sales Area - Retail

Parameter Default Value
Area per Person (sq. ft.) 71.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.11
Power Load Density (W/sq. ft.) 0.10
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Warehouse Lighting - 7 am - 4 pm
Power Schedule Warehouse Lighting - 7 am - 4 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Medium/Bulky Material - Warehouse

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.90
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Warehouse Lighting - 7 am - 4 pm
Power Schedule Warehouse Lighting - 7 am - 4 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Merchandising Sales Area - Retail

Parameter Default Value
Area per Person (sq. ft.) 71.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.14
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Museum and Gallery - Storage

Parameter Default Value
Area per Person (sq. ft.) 215.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.84
Power Load Density (W/sq. ft.) 0.20
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Nurse Station - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.00
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Office - Enclosed

Parameter Default Value
Area per Person (sq. ft.) 215.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Office - Open Plan

Parameter Default Value
Area per Person (sq. ft.) 215.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Office - Common Activity Areas - Inactive Storage

Parameter Default Value
Area per Person (sq. ft.) 358.80
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.28
Power Load Density (W/sq. ft.) 0.20
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Warehouse Lighting - 7 am - 4 pm
Power Schedule Warehouse Lighting - 7 am - 4 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Operating Room - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.20
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 4.000000 Outdoor Air Method
Outdoor Air Method by People and by Area

Other Televised Playing Area - Sports Arena

Parameter Default Value
Area per Person (sq. ft.) 7.18
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.40
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.30
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Parking Area - Attendant Only - Parking Garage

Parameter Default Value
Area per Person (sq. ft.) 215.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.19
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Parking Area - Pedestrian - Parking Garage

Parameter Default Value
Area per Person (sq. ft.) 215.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.20
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Patient Room - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.70
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Personal Services Sales Area - Retail

Parameter Default Value
Area per Person (sq. ft.) 71.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.14
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Pharmacy - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.20
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Physical Therapy - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.90
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Playing Area Gymnasium

Parameter Default Value
Area per Person (sq. ft.) 35.88
Sensible Heat Gain per person (W) 208.08
Latent Heat per person (W) 319.45
Lighting Load Density (W/sq. ft.) 1.40
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.30
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Plenum

Parameter Default Value
Area per Person (sq. ft.) 0.00
Sensible Heat Gain per person (W) 0.00
Latent Heat per person (W) 0.00
Lighting Load Density (W/sq. ft.) 0.00
Power Load Density (W/sq. ft.) 0.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Off - 24 Hours
Lighting Schedule Off - 24 Hours
Power Schedule Off - 24 Hours
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Police Station Laboratory - Police/Fire Stations

Parameter Default Value
Area per Person (sq. ft.) 43.06
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.39
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 10.00
Outdoor Air per Area (CFM/sq. ft.) 0.18
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Public and Staff Lounge - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 43.06
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.84
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 4.000000
Outdoor Air Method by People and by Area

Reading Area - Library

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.20
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Reception/Waiting - Transportation

Parameter Default Value
Area per Person (sq. ft.) 10.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Reception/Waiting - Motel

Parameter Default Value
Area per Person (sq. ft.) 35.88
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Hotel Occupancy - 24 hrs
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Reception/Waiting - Hotel

Parameter Default Value
Area per Person (sq. ft.) 35.88
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.10
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Hotel Occupancy - 24 hrs
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Recovery - Hospital/Healthcare

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.80
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Restoration - Museum

Parameter Default Value
Area per Person (sq. ft.) 26.91
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.70
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Restrooms

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.90
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Ring Sports Area - Sports Arena

Parameter Default Value
Area per Person (sq. ft.) 15.38
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.70
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.30
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Sleeping Quarters - Police/Fire Station

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 30.77
Lighting Load Density (W/sq. ft.) 0.30
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Sorting Area - Post Office

Parameter Default Value
Area per Person (sq. ft.) 215.28
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.20
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 2.000000
Outdoor Air Method by People and by Area

Specialty Store Sales Area - Retail

Parameter Default Value
Area per Person (sq. ft.) 71.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.14
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Stacks - Library

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.70
Power Load Density (W/sq. ft.) 1.50
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.12
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Stairs - Inactive

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.56
Power Load Density (W/sq. ft.) 0.20
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Stairway

Parameter Default Value
Area per Person (sq. ft.) 107.64
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 0.60
Power Load Density (W/sq. ft.) 0.30
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Common Office Occupancy - 8 am - 5 pm
Lighting Schedule Office Lighting - 6 am - 11 pm
Power Schedule Office Lighting - 6 am - 11 pm
Outdoor Air per Person (cu. ft./min) 0.00
Outdoor Air per Area (CFM/sq. ft.) 0.00
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Supermarket Sales Area - Retail

Parameter Default Value
Area per Person (sq. ft.) 134.55
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.10
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Retail Facility Occupancy - 7 am - 8 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Terminal - Ticket Counter - Transportation

Parameter Default Value
Area per Person (sq. ft.) 10.76
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.50
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Health-Care Facility Occupancy - 8 am - 9 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 7.50
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Workshop - Workshop

Parameter Default Value
Area per Person (sq. ft.) 53.82
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 1.90
Power Load Density (W/sq. ft.) 1.00
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Warehouse Occupancy - 7 am - 4 pm
Lighting Schedule Warehouse Lighting - 7 am - 4 pm
Power Schedule Warehouse Lighting - 7 am - 4 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area

Worship - Pulpit Choir - Religious

Parameter Default Value
Area per Person (sq. ft.) 8.91
Sensible Heat Gain per person (W) 73.27
Latent Heat per person (W) 58.61
Lighting Load Density (W/sq. ft.) 2.40
Power Load Density (W/sq. ft.) 0.54
Plenum Lighting Contribution 20.0000%
Occupancy Schedule Large Assembly Hall Occupancy - 8 am - 10 pm
Lighting Schedule Retail Lighting - 7 am - 8 pm
Power Schedule Retail Lighting - 7 am - 8 pm
Outdoor Air per Person (cu. ft./min) 5.00
Outdoor Air per Area (CFM/sq. ft.) 0.06
Air Changes per Hour 0.000000
Outdoor Air Method by People and by Area