You can change the default values for many of the space type parameters.
The following tables list the default settings for space types in Revit. See About Default Building Type and Space Type Parameters.
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 358.80 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.80 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Warehouse Lighting - 7 am - 4 pm |
| Power Schedule | Warehouse Lighting - 7 am - 4 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 358.80 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.90 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 10.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.00 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 10.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.60 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 32.62 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.20 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 32.62 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.60 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.70 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.40 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Commercial Occupancy - 7 am - 6 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.40 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.70 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 1.20 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 2.60 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 8.97 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 1.70 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy- 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 21.53 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 15.38 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 35.88 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 1.49 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 215.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.50 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 43.06 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.00 |
| Power Load Density (W/sq. ft.) | 2.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 16.56 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 16.56 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.40 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | School Occupancy - 8 am - 9 pm |
| Lighting Schedule | School Lighting - 7 am - 9 pm |
| Power Schedule | School Lighting - 7 am - 9 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 43.06 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 43.06 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.90 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 21.53 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.50 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.50 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.00 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 35.88 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.30 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.30 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 15.38 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.90 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 71.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.10 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 15.38 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 80.59 |
| Lighting Load Density (W/sq. ft.) | 0.90 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Restaurant Occupancy - Lunch and Dinner |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 15.38 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 80.59 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Restaurant Occupancy - Lunch and Dinner |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 15.38 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 80.59 |
| Lighting Load Density (W/sq. ft.) | 2.10 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Restaurant Occupancy - Lunch and Dinner |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 15.38 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 80.59 |
| Lighting Load Density (W/sq. ft.) | 1.40 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Restaurant Occupancy - Lunch and Dinner |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 15.38 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 80.59 |
| Lighting Load Density (W/sq. ft.) | 1.20 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Hotel Occupancy - 24 hrs |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 10.76 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 80.59 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 10.76 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 80.59 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 10.76 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 80.59 |
| Lighting Load Density (W/sq. ft.) | 10.93 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Restaurant Occupancy - Lunch and Dinner |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 45.43 |
| Lighting Load Density (W/sq. ft.) | 1.11 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Home Occupancy - 24 hrs |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 45.43 |
| Lighting Load Density (W/sq. ft.) | 1.11 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.60 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 358.80 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.50 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Restaurant Occupancy - Lunch and Dinner |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.20 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.70 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 358.80 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.20 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.50 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 35.88 |
| Sensible Heat Gain per person (W) | 208.08 |
| Latent Heat per person (W) | 319.45 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 20.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 35.88 |
| Sensible Heat Gain per person (W) | 208.08 |
| Latent Heat per person (W) | 319.45 |
| Lighting Load Density (W/sq. ft.) | 0.90 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 20.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 21.53 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 8.97 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.90 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.40 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Warehouse Lighting - 7 am - 4 pm |
| Power Schedule | Warehouse Lighting - 7 am - 4 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 71.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.80 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.20 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Restaurant Occupancy - Lunch and Dinner |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.70 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.70 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.20 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 26.91 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.00 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.60 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 358.80 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.40 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.40 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 3.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 21.53 |
| Sensible Heat Gain per person (W) | 65.94 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Hotel Occupancy - 24 hrs |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 358.80 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.30 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Warehouse Lighting - 7 am - 4 pm |
| Power Schedule | Warehouse Lighting - 7 am - 4 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 21.53 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 215.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.40 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 4.72 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 139.21 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 3.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 80.59 |
| Latent Heat per person (W) | 139.21 |
| Lighting Load Density (W/sq. ft.) | 0.60 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 43.06 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 45.43 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Hotel Occupancy - 24 hrs |
| Lighting Schedule | Residential Lighting - All Day |
| Power Schedule | Residential Lighting - All Day |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 45.43 |
| Lighting Load Density (W/sq. ft.) | 1.11 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Hotel Occupancy - 24 hrs |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 45.43 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Hotel Occupancy - 24 hrs |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.30 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 35.88 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Hotel Occupancy - 24 hrs |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 43.06 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.21 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 26.91 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.70 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 71.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.11 |
| Power Load Density (W/sq. ft.) | 0.10 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Warehouse Lighting - 7 am - 4 pm |
| Power Schedule | Warehouse Lighting - 7 am - 4 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.90 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Warehouse Lighting - 7 am - 4 pm |
| Power Schedule | Warehouse Lighting - 7 am - 4 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 71.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 215.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.84 |
| Power Load Density (W/sq. ft.) | 0.20 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.00 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 215.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 215.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 358.80 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.28 |
| Power Load Density (W/sq. ft.) | 0.20 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Warehouse Lighting - 7 am - 4 pm |
| Power Schedule | Warehouse Lighting - 7 am - 4 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.20 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 4.000000 Outdoor Air Method |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 7.18 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.40 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.30 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 215.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.19 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 215.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.20 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.70 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 71.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.20 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.90 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 35.88 |
| Sensible Heat Gain per person (W) | 208.08 |
| Latent Heat per person (W) | 319.45 |
| Lighting Load Density (W/sq. ft.) | 1.40 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.30 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 0.00 |
| Sensible Heat Gain per person (W) | 0.00 |
| Latent Heat per person (W) | 0.00 |
| Lighting Load Density (W/sq. ft.) | 0.00 |
| Power Load Density (W/sq. ft.) | 0.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Off - 24 Hours |
| Lighting Schedule | Off - 24 Hours |
| Power Schedule | Off - 24 Hours |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 43.06 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.39 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 10.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.18 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 43.06 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.84 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 4.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.20 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 10.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 35.88 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Hotel Occupancy - 24 hrs |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 35.88 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.10 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Hotel Occupancy - 24 hrs |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.80 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 26.91 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.70 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.90 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 15.38 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.70 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.30 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 30.77 |
| Lighting Load Density (W/sq. ft.) | 0.30 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 215.28 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.20 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 2.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 71.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.70 |
| Power Load Density (W/sq. ft.) | 1.50 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.12 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.20 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 107.64 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 0.60 |
| Power Load Density (W/sq. ft.) | 0.30 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Common Office Occupancy - 8 am - 5 pm |
| Lighting Schedule | Office Lighting - 6 am - 11 pm |
| Power Schedule | Office Lighting - 6 am - 11 pm |
| Outdoor Air per Person (cu. ft./min) | 0.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.00 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 134.55 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.10 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Retail Facility Occupancy - 7 am - 8 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 10.76 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.50 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Health-Care Facility Occupancy - 8 am - 9 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 7.50 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 53.82 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 1.90 |
| Power Load Density (W/sq. ft.) | 1.00 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Warehouse Occupancy - 7 am - 4 pm |
| Lighting Schedule | Warehouse Lighting - 7 am - 4 pm |
| Power Schedule | Warehouse Lighting - 7 am - 4 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |
| Parameter | Default Value |
|---|---|
| Area per Person (sq. ft.) | 8.91 |
| Sensible Heat Gain per person (W) | 73.27 |
| Latent Heat per person (W) | 58.61 |
| Lighting Load Density (W/sq. ft.) | 2.40 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Plenum Lighting Contribution | 20.0000% |
| Occupancy Schedule | Large Assembly Hall Occupancy - 8 am - 10 pm |
| Lighting Schedule | Retail Lighting - 7 am - 8 pm |
| Power Schedule | Retail Lighting - 7 am - 8 pm |
| Outdoor Air per Person (cu. ft./min) | 5.00 |
| Outdoor Air per Area (CFM/sq. ft.) | 0.06 |
| Air Changes per Hour | 0.000000 |
| Outdoor Air Method | by People and by Area |