About Considerations Prior to Exporting Duct System Data

Prior to exporting duct system data, each system must have at least one start point and one endpoint. A system is defined as any ductwork between a start point and one or more endpoints. A start point must consist of a fan or other air handling device. Endpoints must consist of outlet devices such as air terminals. Flow values must be assigned to outlet devices in order to properly size system components.

For example, a supply system uses an air handling unit to supply air to several rooms. Each room includes an air terminal as the outlet for the air. In this example, the system includes all ductwork from the air handling unit to each air terminal. If there was no air handling unit in the drawing, you would not be able to export the system data.

You should also consider these factors prior to exporting data:

Prior to exporting, you should also consult your external analysis package for any additional requirements you must include in your system. For example, you may need to specify the ASHRAE fitting type for all duct fittings as shown in Specifying ASHRAE Fitting Types. There may also be system design constraints that you need to consider.

Tip: To preview the connectivity of a system, select an object within the system, and click [Duct, Duct Flex, or Duct Fitting] tabModify panelShow Connected Objects drop-downShow Connected Run.