A parallel fan powered box has a fan that runs only during the heating mode to pull warm return air from the ceiling plenum.
The air flow is sized for the sensible peak on a traditional air system, and ventilation for a dedicated outdoor air system (DOAS) only.
| Property | Value | Notes |
|---|---|---|
| Cooling supply air temperature | N/A | Determined by the air system (typically 12.7778°C). |
| Heating supply air temperature | 40°C |
The reheat coil has the following assumptions.
| Property | Value | Notes |
|---|---|---|
| Coil entering air temperature | Varied | Determined by the air system (typically between 12.7778°C and 18.3333°C by default). |
| Coil leaving air temperature | 40°C | |
| Hot water design inlet temperature | N/A | Set by the hot water loop if hot water coil is used in the system. |
| Hot water design outlet temperature | N/A | Set by the hot water loop if hot water coil is used in the system. |
The supply fan has the following properties.
| Property | Value | Notes |
|---|---|---|
| Pressure Rise | 250 Pa | |
| Total Efficiency | 70% | |
| Motor Efficiency | 94% | |
| Flow Mode | Constant |