Variable Refrigerant Flow Fan Coil

Variable refrigerant flow (VRF) systems vary the flow of refrigerant to indoor units based on demand.

Required Objects

The variable refrigerant flow (VRF) fan coil must have the following properties.
  • It must be attached to a conditioned zone.
  • It must be connected to a variable refrigerant flow loop.

Design Assumptions

Property Value Notes
System air flow Constant
Cooling supply air temperature 12.78°C
Heating supply air temperature 40°C

Cooling Coil

The cooling coil has the following assumptions:
Property Value Notes
Coil leaving air temperature 12.78°C

Heating Coil

The heating coil has the following assumptions.
Property Value Notes
Coil leaving air temperature 40°C

Supplemental Heating Coil

This is an electric resistance coil with an efficiency of 1.0.

Supply Fan

The supply fan has the following properties.

Property Value Notes
Pressure rise 250 Pa
Total efficiency 70%
Motor efficiency 90%