Air System

In systems analysis, the air system is an object that is used to represent a single- or multi-zone air handling unit that can operate as a traditional system designed for ventilation and space conditioning or as a dedicated outdoor air system (DOAS).

Required Objects

The air system must have the following properties.
  • It must have at least 1 piece of zone equipment that is connected to a conditioned space.
  • It must have at least a fan, but typically also has other objects such as a heating and cooling coil.

Design Assumptions

Property Value Notes
Chilled water design inlet temperature N/A Set by chilled water loop if chilled water coil is used in system.
Chilled water design outlet temperature N/A Set by chilled water loop if chilled water coil is used in system.
Cooling supply air temperature 12.7778°C
Heating supply inlet air temperature 4°C Assumes all heating occurs at the zonal reheat.
Heating supply outlet air temperature 12.7778°C Preheat on the incoming air stream, not the mixed.
Hot water design inlet temperature N/A Set by hot water loop if hot water coil is used in system.
Hot water design outlet temperature N/A Set by hot water loop if hot water coil is used in system.

Configuration

The air system is comprised of 6 main components.
  1. A preheat coil
  2. A heat exchanger
  3. An outdoor air controller
  4. A cooling coil
  5. A heating coil
  6. A supply fan

Preheat Coil

If a preheat coil is present, the following assumptions are made.
  • It is located before the heat exchanger (if present) to prevent any frost issues.
  • The coil entering air temperature is equal to the design day temperature.
  • The coil leaving air temperature is 4°C.
  • If the coil is a hot water coil, it is assumed that hot water is supplied at 60°C with a return temperature of 43.33°C.

Heat Exchanger

The heat exchanger has the following assumptions.
  • The heat exchanger controls the bypass air ratio, per the needs of the system-requested supply air temperature at a given timestep.
Heat Exchanger Type
Sensible Enthalpy
Sensible effectiveness at 100% heating air flow 0.76 0.76
Sensible effectiveness at 75% heating air flow 0.81 0.81
Latent effectiveness at 100% heating air flow 0 0.68
Latent effectiveness at 75% heating air flow 0 0.73
Sensible effectiveness at 100% cooling air flow 0.76 0.76
Sensible effectiveness at 75% cooling air flow 0.81 0.81
Latent effectiveness at 100% cooling air flow 0 0.68
Latent effectiveness at 75% cooling air flow 0 0.73

Outdoor Air Controller

The outdoor air controller has the following assumptions.
  • Has an economizer that modulates flow based on a differential enthalpy control.
  • Has a bypass around the heat exchanger (if present) when the economizer is active.
  • When operating as a DOAS, the unit is 100% outdoor air.
  • The system has demand-controlled ventilation (DCV).

Cooling Coil

The cooling coil has the following assumptions.
  • The DX coil is single speed with a rated COP of 3.0.
    • The sensible-to-latent heat ratio is auto-sized to meet the system needs during sizing.
  • The chilled water coil has the following assumptions.
Property Value Notes
Coil entering air temperature N/A Determined by the design day.
Coil leaving air temperature ~11.11°C Calculated from the air system supply air temperature minus fan heat generated (typically about 1.5°C - 2°C).
Chilled water design inlet temperature N/A Set by chilled water loop if chilled water coil is used in system.
Chilled water design outlet temperature N/A Set by chilled water loop if chilled water coil is used in system.

Heating Coil

The heating coil has the following assumptions.
  • The electric resistance heating coil is 100% efficient.
  • The furnace heating coil is 80% efficient.
  • The hot water coil has the following properties.
Property Value Notes
Coil entering air temperature Varied 4°C with preheat coil, otherwise it is determined by the design day.
Coil leaving air temperature Varied 12.7778°C if a traditional air system, 15.5556°C if it is a DOAS.
Hot water design inlet temperature N/A Set by the hot water loop if a hot water coil is used in the system.
Hot water design outlet temperature N/A Set by the hot water loop if a hot water coil is used in the system.

Supply Fan

The supply fan can be either constant or variable volume with the following properties.

Property Value Notes
Pressure rise 996 Pa
Total efficiency 0.6
Motor efficiency 0.94
Minimum flow fraction 0.3 Only for variable volume fans.