Passive Chilled Beam

A passive chilled beam is normally suspended from a ceiling and consists of a heat exchanger in a housing, but does not contains an integral air supply like an active chilled beam.

Required Objects

The passive chilled beam must have the following properties.
  • It must be connected to a hot water loop.
  • It must be connected to a chilled water loop.
  • It must be connected to a conditioned zone.

Design Assumptions

  • The passive chilled beam is modeled as a four pipe fan coil with no fan power at the moment.
Property Value Notes
Cooling discharge air temperature 17°C This is passive air movement.
Heating discharge air temperature 29.44°C This is passive air movement.

Cooling Coil

The cooling coil has the following assumptions.

Property Value Notes
Coil entering air temperature N/A Mix of air system and induced zone temperature.
Design coil leaving air temperature 17°C It is on the colder side of discharge temperatures.
Chilled water design inlet temperature N/A Set by the chilled water loop.
Chilled water design outlet temperature N/A Set by the chilled water loop.

Heating Coil

The heating coil has the following assumptions.

Property Value Notes
Coil entering air temperature N/A Mix of air system and induced zone temperature.
Design coil leaving air temperature 29.44°C
Hot water design inlet temperature N/A Set by the hot water loop.
Hot water design outlet temperature N/A Set by the hot water loop.