A passive chilled beam is normally suspended from a ceiling and consists of a heat exchanger in a housing, but does not contains an integral air supply like an active chilled beam.
| Property | Value | Notes | 
|---|---|---|
| Cooling discharge air temperature | 17°C | This is passive air movement. | 
| Heating discharge air temperature | 29.44°C | This is passive air movement. | 
The cooling coil has the following assumptions.
| Property | Value | Notes | 
|---|---|---|
| Coil entering air temperature | N/A | Mix of air system and induced zone temperature. | 
| Design coil leaving air temperature | 17°C | It is on the colder side of discharge temperatures. | 
| Chilled water design inlet temperature | N/A | Set by the chilled water loop. | 
| Chilled water design outlet temperature | N/A | Set by the chilled water loop. | 
The heating coil has the following assumptions.
| Property | Value | Notes | 
|---|---|---|
| Coil entering air temperature | N/A | Mix of air system and induced zone temperature. | 
| Design coil leaving air temperature | 29.44°C | |
| Hot water design inlet temperature | N/A | Set by the hot water loop. | 
| Hot water design outlet temperature | N/A | Set by the hot water loop. |