Hot Water Loop

The hot water loop uses a boiler and a variable speed pump to supply hot water.

Required Objects

The hot water loop must have the following property.
  • It must have at least 1 hot water coil attached to the loop.

Design Assumptions

Property Value Notes
Loop supply temperature 60°C Determined by the air system (typically 12.7778°C).
Loop return temperature 43.33°C Determined by the air system (typically between 12.7778°C and 18.3333°C by default).

Configuration

The hot water loop is comprised of 2 main components.

  1. Boiler
  2. Pump

Boiler

The boiler has operating temperatures typical of a condensing-style boiler.

Property Value Notes
Leaving water temperature 60°C Determined by the loop design above.
Thermal efficiency 0.92
Flow control Variable Modulates flow to meet set point.

Pump

The pump has the following assumptions when it is in the default configuration.

Pressure rise 179344.014 Pa
Motor efficiency 90%
Flow type Variable speed
Flow control Intermittent Only runs when there is demand.