The hot water loop uses a boiler and a variable speed pump to supply hot water.
Property | Value | Notes |
---|---|---|
Loop supply temperature | 60°C | Determined by the air system (typically 12.7778°C). |
Loop return temperature | 43.33°C | Determined by the air system (typically between 12.7778°C and 18.3333°C by default). |
The hot water loop is comprised of 2 main components.
The boiler has operating temperatures typical of a condensing-style boiler.
Property | Value | Notes |
---|---|---|
Leaving water temperature | 60°C | Determined by the loop design above. |
Thermal efficiency | 0.92 | |
Flow control | Variable | Modulates flow to meet set point. |
The pump has the following assumptions when it is in the default configuration.
Pressure rise | 179344.014 Pa | |
Motor efficiency | 90% | |
Flow type | Variable speed | |
Flow control | Intermittent | Only runs when there is demand. |