Four Pipe Fan Coil

Fan coils provide conditioned air to an area by recirculating air through the coils. A four-pipe fan coil unit consists of a fan, air filter, chilled water cooling coil, and hot water heating coil.

Required Objects

The four pipe fan coil must have the following properties.
  • It must be connected to a hot water loop.
  • It must be connected to a chilled water loop.
  • It must be attached to a conditioned zone.

Design Assumptions

If the Draw Ventilation property is selected, the following will occur.

If the Draw Ventilation property is not selected, the following will occur.

Property Value Notes
System air flow Constant
Cooling supply air temperature 12.78°C
Heating supply air temperature 40°C

Cooling Coil

The cooling coil has the following assumptions.

Property Value Notes
Design coil leaving air temperature 12.78°C
Chilled water design inlet temperature N/A Set by the chilled water loop.
Chilled water design outlet temperature N/A Set by the chilled water loop.

Heating Coil

The heating coil has the following assumptions.

Property Value Notes
Coil leaving air temperature 40°C
Hot water design inlet temperature N/A Set by the hot water loop.
Hot water design outlet temperature N/A Set by the hot water loop.

Supply Fan

The supply fan has the following assumptions.

Property Value Notes
Pressure rise 250 Pa
Total efficiency 70%
Motor efficiency 94%