Fan coils provide conditioned air to an area by recirculating air through the coils. A four-pipe fan coil unit consists of a fan, air filter, chilled water cooling coil, and hot water heating coil.
If the Draw Ventilation property is selected, the following will occur.
If the Draw Ventilation property is not selected, the following will occur.
Property | Value | Notes |
---|---|---|
System air flow | Constant | |
Cooling supply air temperature | 12.78°C | |
Heating supply air temperature | 40°C |
The cooling coil has the following assumptions.
Property | Value | Notes |
---|---|---|
Design coil leaving air temperature | 12.78°C | |
Chilled water design inlet temperature | N/A | Set by the chilled water loop. |
Chilled water design outlet temperature | N/A | Set by the chilled water loop. |
The heating coil has the following assumptions.
Property | Value | Notes |
---|---|---|
Coil leaving air temperature | 40°C | |
Hot water design inlet temperature | N/A | Set by the hot water loop. |
Hot water design outlet temperature | N/A | Set by the hot water loop. |
The supply fan has the following assumptions.
Property | Value | Notes |
---|---|---|
Pressure rise | 250 Pa | |
Total efficiency | 70% | |
Motor efficiency | 94% |