The Variable Refrigerant Flow (VRF) loop has a VRF condenser. As an option, the condenser may be water-cooled, in which case it is attached to a condenser loop.
Property | Value | Notes |
---|---|---|
Rated cooling COP | 3.3 | |
Rated heating COP | 3.5 | |
Minimum outdoor air temperature in heating | -20°C | |
Low temperature loop return temperature | 15.5556°C | Set by hot water loop if hot water coil is used in system |
The heating coil has the following assumptions.
Property | Value | Notes |
---|---|---|
Coil leaving air temperature | 40°C |
This is an electric resistance coil with an efficiency of 1.0
The supply fan has the following properties.
Property | Value | Notes |
---|---|---|
Pressure rise | 250 Pa | |
Total efficiency | 70% | |
Motor efficiency | 90% |