Variable Refrigerant Flow Loop

The Variable Refrigerant Flow (VRF) loop has a VRF condenser. As an option, the condenser may be water-cooled, in which case it is attached to a condenser loop.

Required Objects

The VRF loop must have the following property.
  • It must have at least one VRF Fan Coil Unit attached to the loop.

Design Assumptions

Property Value Notes
Rated cooling COP 3.3
Rated heating COP 3.5
Minimum outdoor air temperature in heating -20°C
Low temperature loop return temperature 15.5556°C Set by hot water loop if hot water coil is used in system

Heating Coil

The heating coil has the following assumptions.

Property Value Notes
Coil leaving air temperature 40°C

Supplemental Heating Coil

This is an electric resistance coil with an efficiency of 1.0

Supply Fan

The supply fan has the following properties.

Property Value Notes
Pressure rise 250 Pa
Total efficiency 70%
Motor efficiency 90%