A water source heat pump operates like a traditional air source heat pump, but it extracts and dissipates heat by way of water instead of air.
The water source heat pump (WSHP) must have the following properties.
Property | Value | Notes |
---|---|---|
System air flow | Constant | |
Cooling supply air temperature | 12.78C | |
Heating supply air temperature | 40C |
Cooling Coil
Property | Value | Notes |
---|---|---|
Coil leaving air temperature | 12.78°C | |
COP | 3.0 |
Heating Coil
Property | Value | Notes |
---|---|---|
Coil leaving air temperature | 40°C | |
COP | 3.0 |
Supplemental Heating Coil
This is an electric resistance coil with an efficiency of 1.0.
Supply Fan
The supply fan has the following properties.
Property | Value | Notes |
---|---|---|
Pressure rise | 300 Pa | |
Total efficiency | 60% | |
Motor efficiency | 80% |