A packaged terminal air conditioner (PTAC) is a type of self-contained heating and air-conditioning system. Some PTACs are cooling-only type.
If the Draw Ventilation property is selected, the following will occur.
If the Draw Ventilation property is not selected, the following will occur.
Property | Value | Notes |
---|---|---|
System air flow | Constant | |
Cooling supply air temperature | 12.78°C | |
Heating supply air temperature | 40°C |
The cooling coil has the following assumptions.
Property | Value | Notes |
---|---|---|
Coil leaving air temperature | 12.78°C | |
Chilled water design inlet temperature | 3.0 |
The heating coil has the following assumptions.
Property | Value | Notes |
---|---|---|
Coil leaving air temperature | 40°C | |
Hot water design inlet temperature | N/A | Set by the hot water loop. |
Hot water design outlet temperature | N/A | Set by the hot water loop. |
The supply fan has the following properties.
Property | Value | Notes |
---|---|---|
Pressure rise | 250 Pa | |
Total efficiency | 70% | |
Motor efficiency | 94% |