Unit ventilators provide a controlled means of introducing conditioned outdoor air during the heating season.
If the Draw Ventilation property is selected, the following will occur.
If the Draw Ventilation property is not selected, the following will occur.
Property | Value | Notes |
---|---|---|
System air flow | Constant | |
Cooling supply air temperature | 12.78°C | |
Heating supply air temperature | 40°C |
The cooling coil has the following assumptions.
Property | Value | Notes |
---|---|---|
Coil entering air temperature | N/A | Determined by the design day. |
Coil leaving air temperature | ~11.11°C | Calculated from the air system supply air temperature minus fan heat generated (typically about 1.5°C - 2°C). |
Chilled water design inlet temperature | N/A | Set by the chilled water loop if chilled water coil is used in the system. |
Chilled water design outlet temperature | N/A | Set by the chilled water loop if chilled water coil is used in the system. |
The heating coil has the following assumptions.
Property | Value | Notes |
---|---|---|
Coil leaving air temperature | 40°C | |
Hot water design inlet temperature | N/A | Set by the hot water loop. |
Hot water design outlet temperature | N/A | Set by the hot water loop. |
The supply fan has the following properties:
Property | Value | Notes |
---|---|---|
Pressure rise | 250 Pa | |
Total efficiency | 70% | |
Motor efficiency | 94% |