The variable air volume (VAV) box is an air terminal with turndown on an air system. As an option, it may contain a reheat coil.
Property | Value | Notes |
---|---|---|
Cooling supply air temperature | N/A | Determined by the air system (typically 12.7778°C). |
Heating supply air temperature | 40°C | |
Minimum air flow fraction | 0.3 |
The reheat coil has the following assumptions.
Property | Value | Notes |
---|---|---|
Coil entering air temperature | Varied | Determined by the air system (typically between 12.7778°C and 18.3333°C by default). |
Coil leaving air temperature | 40°C | |
Hot water design inlet temperature | N/A | Set by the hot water loop if a hot water coil is used in the system. |
Hot water design outlet temperature | N/A | Set by the hot water loop if a hot water coil is used in the system. |