Learn about the default settings for space types in
Revit.
You can change the default values for space type parameters. See
Space Properties.
Active Storage
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Warehouse 7 am - 4 pm
|
People/100 sq. M.
|
3.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.8
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Active Storage - Hospital/healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
3.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.9
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Air/Train/Bus - Baggage Area
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
100.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Airport Concourse
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
100
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.6
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Atrium - Each additional floor
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
33.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.2
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Atrium - First 3 floors
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
33.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.6
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Audience/Seating Area - Penitentiary
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
150
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.7
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Audience/Seating Area - Exercise Center
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Audience/Seating Area - Gymnasium
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Commercial 7 am - 6 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.4
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Audience/Seating Area - Sports Arena
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.4
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Audience/Seating Area - Convention Center
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
150
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.7
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Audience/Seating Area - Motion Picture Theatre
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
1.2
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Audience/Seating Area - Performing Arts Theatre
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
2.6
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Audience/Seating Area - Religious
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
120
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
1.7
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Audience/Seating Area - Police/Fire Station
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
50.0
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.93
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Audience/Seating Area - Courthouse
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
70.0
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.93
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Audience/Seating Area - Auditorium
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.93
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Bank Customer Area
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
30.0
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
1.49
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Banking Activity Area - Office
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
5.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.5
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.3
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Barber and Beauty Parlor
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
25.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1
|
Power Load Density (W/sq. ft.)
|
2
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Card File and Cataloguing - Library
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Classroom/Lecture/Training - Penitentiary
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
65.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Classroom/Lecture/Training
Parameter
|
Default Value
|
Occupancy Schedule
|
School 8 am - 9 pm
|
Power Schedule
|
School 7 am - 9 pm
|
People/100 sq. M.
|
65.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.4
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Confinement Cells - Penitentiary
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
25.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.93
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Confinement Cells - Court House
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
25.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.9
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Conference/Meeting/Multipurpose
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
50.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Corridor/Transition
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.5
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Corridor/Transition - Manufacturing Facility
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
00.5
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Corridor w/Patient Waiting Exam - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Court Sports Area - Sports Area
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
30.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.3
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Courtroom - Court House
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
70.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.3
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Department Store Sales - Retail
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
15.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.14
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Detailed - Manufacturing Facility
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.1
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dining Area
Parameter
|
Default Value
|
Occupancy Schedule
|
Restaurant Lunch and Dinner
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
70.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
275
|
Lighting Load Density (W/sq. ft.)
|
0.9
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Dining Area - Hotel
Parameter
|
Default Value
|
Occupancy Schedule
|
Restaurant Lunch and Dinner
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
70.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
275
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Dining Area - Family Dining
Parameter
|
Default Value
|
Occupancy Schedule
|
Restaurant Lunch and Dinner
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
70.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
275
|
Lighting Load Density (W/sq. ft.)
|
2.1
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Dining Area - Lounge/Leisure Dining
Parameter
|
Default Value
|
Occupancy Schedule
|
Restaurant Lunch and Dinner
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
70.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
275
|
Lighting Load Density (W/sq. ft.)
|
1.4
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dining Area - Motel
Parameter
|
Default Value
|
Occupancy Schedule
|
Hotel 24 hrs
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
70.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
275
|
Lighting Load Density (W/sq. ft.)
|
1.2
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dining Area - Transportation
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
100.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
275
|
Lighting Load Density (W/sq. ft.)
|
0.93
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dining Area - Penitentiary
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
100.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
275
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dining Area - Civil Services
Parameter
|
Default Value
|
Occupancy Schedule
|
Restaurant Lunch and Dinner
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
100.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
275
|
Lighting Load Density (W/sq. ft.)
|
0.93
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dormitory Bedroom
Parameter
|
Default Value
|
Occupancy Schedule
|
Home 24 hrs
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
155
|
Lighting Load Density (W/sq. ft.)
|
1.11
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Dormitory Study Hall
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
155
|
Lighting Load Density (W/sq. ft.)
|
1.11
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Dressing/Locker/Fitting Room - Gymnasium
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.6
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dressing/Locker/Fitting Room - Court House
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Lighting Schedule
|
Office Lighting 6 am - 11 pm
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.56
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dressing/Locker/Fitting Room - Performing Arts Theatre
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.56
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dressing/Locker/Fitting Room - Auditorium
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.56
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Dressing/Locker/Fitting Room - Exercise Center
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.56
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Electrical/Mechanical
Parameter
|
Default Value
|
Occupancy Schedule
|
Restaurant Lunch and Dinner
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
3.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.5
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Elevator Lobbies
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
0.2
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Emergency - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.7
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Equipment Room - Manufacturing Facility
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
3.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.2
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Exam/Treatment - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.5
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Exercise Area - Exercise Center
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
30.0
|
People Sensible Heat Gain (Btu/hr)
|
710
|
People Latent Heat Gain (Btu/hr)
|
1090
|
Lighting Load Density (W/sq. ft.)
|
0.93
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Exercise Area - Gymnasium
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
30.0
|
People Sensible Heat Gain (Btu/hr)
|
710
|
People Latent Heat Gain (Btu/hr)
|
1090
|
Lighting Load Density (W/sq. ft.)
|
0.9
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Exhibit Space - Convention Center
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
50.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Fellowship Hall - Religious Buildings
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
120.0
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.9
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Fine Material - Warehouse
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Warehouse 7 am - 4 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.4
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Fine Merchandise - Sales Area Retail
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
15.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.14
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Fire Station Engine Room - Police Fire Station
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.8
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Food Preparation
Parameter
|
Default Value
|
Occupancy Schedule
|
Restaurant Lunch and Dinner
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.2
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Garage Service/Repair - Automotive Facility
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.7
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
General High Bay - Manufacturing Facility
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.7
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
General Low Bay - Manufacturing Facility
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.2
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
General Exhibition - Museum
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
40.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Hospital - Nursery - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.6
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Hospital - Medical Supplies - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
3.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.4
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Hospital/Radiology- Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.4
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Hotel/Conference Center - Conference/Meeting
Parameter
|
Default Value
|
Occupancy Schedule
|
Hotel 24 hrs
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
50.0
|
People Sensible Heat Gain (Btu/hr)
|
225
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Inactive Storage
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Warehouse 7 am - 4 pm
|
People/100 sq. M.
|
3.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.3
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Judges Chambers - Court House
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
50.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Laboratory - Office
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
5.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.4
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Laundry - Ironing and Sorting
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
475
|
Lighting Load Density (W/sq. ft.)
|
0.56
|
Power Load Density (W/sq. ft.)
|
3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Laundry - Washing - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
275
|
People Latent Heat Gain (Btu/hr)
|
475
|
Lighting Load Density (W/sq. ft.)
|
0.6
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Library - Audio Visual - Library - Audio Visual
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
25.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Living Quarters - Dormitory
Parameter
|
Default Value
|
Occupancy Schedule
|
Hotel 24 hrs
|
Power Schedule
|
Residential Lighting All Day
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
155
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Living Quarters - Motel
Parameter
|
Default Value
|
Occupancy Schedule
|
Hotel 24 hrs
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
155
|
Lighting Load Density (W/sq. ft.)
|
1.11
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Living Quarters - Hotel
Parameter
|
Default Value
|
Occupancy Schedule
|
Hotel 24 hrs
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
155
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Lobby
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
150.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
155
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Lobby - Religious Building
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Lobby - Motion Picture Theatre
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Lobby - Auditorium
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Lobby - Performing Arts Theatre
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
3.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Lobby - Post Office
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
150.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.3
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Lobby - Hotel
Parameter
|
Default Value
|
Occupancy Schedule
|
Hotel 24 hrs
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
150.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Lounge or Recreation
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
30.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.21
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Mail Concourse Sales Area - Retail
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
40.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.7
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Mass Merchandising Sales Area - Retail
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Warehouse 7 am - 4 pm
|
People/100 sq. M.
|
15.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.11
|
Power Load Density (W/sq. ft.)
|
0.1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Medium/Bulky Material - Warehouse
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Warehouse 7 am - 4 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.9
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Merchandising Sales Area - Retail
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
15.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.14
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Museum and Gallery - Storage
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
5.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.84
|
Power Load Density (W/sq. ft.)
|
0.2
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Nurse Station - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.3
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Office - Enclosed
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
5.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.3
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Office - Open Plan
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
5.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.3
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Office - Common Activity Areas - Inactive Storage
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Warehouse 7 am - 4 pm
|
People/100 sq. M.
|
3.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.28
|
Power Load Density (W/sq. ft.)
|
0.2
|
Electrical Equipment Radiant Percentage
|
0.3
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Operating Room - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.2
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Other Televised Playing Area - Sports Arena
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
150.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.4
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Parking Area - Attendant Only - Parking Garage
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
5.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.19
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Parking Area - Pedestrian - Parking Garage
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
5.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.2
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Patient Room - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.7
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Personal Services Sales Area - Retail
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
15.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.14
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Pharmacy - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.2
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Physical Therapy - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.9
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Playing Area Gymnasium
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
30.0
|
People Sensible Heat Gain (Btu/hr)
|
710
|
People Latent Heat Gain (Btu/hr)
|
1090
|
Lighting Load Density (W/sq. ft.)
|
1.4
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Plenum
Parameter
|
Default Value
|
Occupancy Schedule
|
Cooling/Heating Off 24 hrs
|
Power Schedule
|
Cooling/Heating Off 24 hrs
|
People/100 sq. M.
|
00
|
People Sensible Heat Gain (Btu/hr)
|
0
|
People Latent Heat Gain (Btu/hr)
|
0
|
Lighting Load Density (W/sq. ft.)
|
0
|
Power Load Density (W/sq. ft.)
|
0
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0
|
Carpet (Y/N)
|
N
|
Police Station Laboratory - Police/Fire Stations
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
25.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.39
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Public and Staff Lounge - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
25.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.84
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Reading Area - Library
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.2
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Reception/Waiting - Transportation
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
100.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Reception/Waiting - Motel
Parameter
|
Default Value
|
Occupancy Schedule
|
Hotel 24 hrs
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
30.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Reception/Waiting - Hotel
Parameter
|
Default Value
|
Occupancy Schedule
|
Hotel 24 hrs
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
30.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.1
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Recovery - Hospital/Healthcare
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.8
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Restoration - Museum
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
40.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.7
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Restrooms
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.9
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Ring Sports Area - Sports Arena
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
70.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.7
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Sleeping Quarters - Police/Fire Station
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
105
|
Lighting Load Density (W/sq. ft.)
|
0.3
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Sorting Area - Post Office
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
5.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.2
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Specialty Store Sales Area - Retail
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
15.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.14
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Stacks - Library
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.7
|
Power Load Density (W/sq. ft.)
|
1.5
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Stairs - Inactive
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.56
|
Power Load Density (W/sq. ft.)
|
0.2
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Stairway
Parameter
|
Default Value
|
Occupancy Schedule
|
Common Office 8 am - 5 pm
|
Power Schedule
|
Office Lighting 6 am - 11 pm
|
People/100 sq. M.
|
10.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
0.6
|
Power Load Density (W/sq. ft.)
|
0.3
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Supermarket Sales Area - Retail
Parameter
|
Default Value
|
Occupancy Schedule
|
Retail Facility 7 am - 8 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
8.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.1
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Terminal - Ticket Counter - Transportation
Parameter
|
Default Value
|
Occupancy Schedule
|
Healthcare Facility 8 am - 9 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
100.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.5
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|
Workshop - Workshop
Parameter
|
Default Value
|
Occupancy Schedule
|
Warehouse 7 am - 4 pm
|
Power Schedule
|
Warehouse 7 am - 4 pm
|
People/100 sq. M.
|
20.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
1.9
|
Power Load Density (W/sq. ft.)
|
1
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
N
|
Worship - Pulpit Choir - Religious
Parameter
|
Default Value
|
Occupancy Schedule
|
Large Assembly Hall 8 am - 10 pm
|
Power Schedule
|
Retail Lighting 7 am - 8 pm
|
People/100 sq. M.
|
120.0
|
People Sensible Heat Gain (Btu/hr)
|
250
|
People Latent Heat Gain (Btu/hr)
|
200
|
Lighting Load Density (W/sq. ft.)
|
2.4
|
Power Load Density (W/sq. ft.)
|
0.54
|
Electrical Equipment Radiant Percentage
|
0.5
|
Infiltration Flow (CFM/sq. ft.)
|
0.038
|
Carpet (Y/N)
|
Y
|