Interior and exterior room-bounding components must be correctly identified to create an accurate Systems Analysis. Whenever possible, you should place a space component in cavities, shafts, and chases. However, some areas are too small to allow placing a space.
When this occurs, you can account for the volume of these small spaces using one of two methods:
The size and shape of these small areas determines how to account for the volume.
To clear the Room Bounding parameter for a wall
The shading for the tangent space fills both areas and the volume for the cavity, shaft or chase is automatically included in the tangent space.
To treat the area as a sliver space
It’s often safer to clear the Room Bounding parameter for a particular space than to adjust the Sliver Space Tolerance throughout the model.
The illustration above shows a model that is ready for loads analysis. It shows the floor plan to the left and the analytical model. Spaces have been placed for all of the symmetrical and asymmetrical areas, including the in-place component placed in the opening at the bottom of the model. The space (far left) is not a sliver, because no space exists to the left of the outer wall. The Room Bounding parameter was cleared for the wall separating this area from the tangent spaces. The Room Bounding parameter was also cleared for the walls separating the curved area and small rectangular area at the lower center of the project. When the Room Bounding parameter is cleared, the shading displays for these areas as part of the tangent spaces. Sliver spaces display unshaded in the floor plan view. However, the sliver spaces do display in the analytical model, and they are computed during Systems Analysis.