Valve

A control valve regulates either flow or pressure in a distribution system. Valves are modeled as nodes in InfoWater Pro. Because Valves are link elements in our Analysis EPANET engine, valves are converted to node or point elements by creating hidden junctions to the left and right of the valve that you cannot see in InfoWater Pro, but can be seen in an EPANET export of the model. The elevation of the valve is used as the hidden node elevation and the valve upstream and downstream pressure are calculated from the pressure at the two hidden nodes.

Valve direction is surmised in InfoWater Pro by the direction of the two pipes connected to the valve. Both connected pipes to the valve should be drawn in the direction of expected flow through the valve.

This page contains the following topics:

Types of Valves

There are different valve types that can be used within InfoWater Pro. A discussion of each valve Type available and the data required for each type can be found below.

Pressure Reducing Valves (PRV)

A PRV limits the pressure on the downstream end not to exceed a pre-set value when the upstream pressure is above the setting.

The PRV valve has three potential states the valve can be in: Active, Open, or Closed.

A valve can also override its Status via the initial Status setting or by control to set the valve Open or Closed. If a PRV is set to Open, it will act like an Open pipe.

Specify the Valve Type as Pressure Reducing in the Type field of the Modeling Data section of the Model Explorer - Attribute Tab.

Required Fields:

Optional Fields:

Note: For PRVs please do not enter any data to the Curve, PID, UCL, or LCL fields.

Pressure Sustaining Valves (PSV)

A PSV maintains a minimum pressure on its upstream end when the downstream pressure is below the setting.

The PSV valve has three potential states the valve can be in: Active, Open, or Closed.

A valve can also override its Status via the initial Status setting or by control to set the valve Open or Closed. If a PSV is set to Open, it will act like an Open pipe. If the downstream pressure is above the setting, then flow through the valve is unrestricted. Should the downstream pressure exceed the pressure upstream pressure, then the valve closes to prevent reverse flow.

Specify the Valve Type as Pressure Sustaining in the Type field of the Modeling Data section of the Model Explorer - Attribute Tab.

Required Fields:

Optional Fields:

Note: For PSVs please do not enter any data to the Curve, PID, UCL, or LCL fields.

Pressure Breaker Valves (PBV)

PBV's may be used to force a specified pressure loss to occur across the valve. PBV's do not really exist in the field. They are an abstraction to help model unaccountable pressure losses in the system. Flow can be in either direction through the valve. 

Specify the Valve Type as Pressure Breaker in the Type field of the Modeling Data section of the Model Explorer - Attribute Tab. Required Fields:

Optional Fields:

Note: For PBVs please do not enter any data to the Curve, PID, UCL, or LCL fields.

Flow Control Valves (FCV)

FCV enforce an upper limit of flow based on the defined Setting value for the valve. FCVs do not prevent reverse flow. The application produces a warning message in the Report file if the head necessary to push the specified flow cannot be provided based on the available head upstream of the valve or if the valve has reverse flow. An error of "Open but cannot deliver flow" for a FCV indicates the upstream pressure is insufficient to push the specified setting flow into the system. 

Optional Fields:

Note: For FCVs, do not enter any data into the Curve, PID, UCL , or LCL fields.

Throttle Control Valves (TCV)

A TCV may be used to simulate a partially opened valve by adjusting the minor loss coefficient. They are normally used to increase or decrease flows or to control pressures in the system. A TCV is the best valve to use for modeling normally open system valves as a valve in InfoWater Pro. TCV valves do not restrict reverse flow.

TCVs can be configured with or without a curve:

TCV tips:

Specify the Valve Type as Throttle Control in the Type field of the Modeling Data section of the Model Explorer - Attribute Tab

Required Fields:

Note: For TCVs please do not enter any data to the PID, UCL, or LCL fields.

Minor Loss vs. % Open (Control Valves - Motorized Throttled) Curves for Throttle Control Valves

A relationship between the degree (or percentage) to which a valve is closed and the resulting headloss coefficient is usually available from the valve manufacturer or can be derived from field tests (based on measured flow through the valve, headloss across the valve and percentage (degree) opening setting). Alternately, a curve can be used to define the relationship between valve openings and loss coefficients. In this case, the X values represent the percentage (degree) opening settings and the Y values designate the resulting headloss coefficients. Based on the valve opening settings specified, loss coefficients are directly computed by InfoWater Pro for linearly interpolated values of intermediate percentage (degree) opening settings. When such a curve is used, this type of valves is also referred to as Motorized Throttled Valves (MTV). For Motorized Throttled Valves (MTVs), a Minor Loss Coefficient Curve consists of a collection of points defining the minor loss coefficient K (y-axis) as a function of the percentage (degree) opening setting (x-axis). It provides the capability to model valves with unique headloss characteristics such as cone and butterfly valves. Please limit the maximum minor loss value assigned to the valve to be under 100,000 as higher minor loss values can cause difficulties for EPANET to use. A sample table and curve are provided below:

General Purpose Valves (GPV)

General Purpose valves are used to represent cases where you define the headloss through the valve as a function of the flow. The GPV requires the assignment of the Headloss vs. Flow curve. A GPV may be used to model turbines, well draw-down or reduced-flow backflow prevention valves. This relationship is defined using a curve.

GPV tips:

Specify the Valve Type as General Purpose in the Type field of the Modeling Data section of the Model Explorer - Attribute Tab

Required Fields:

Note: For GPVs ,please do not enter any data to the Setting, Minor Loss, PID, UCL, or LCL fields.

Headloss vs. Flow (Control Valves - General Purpose, Float) Curves for General Purpose Valves and Float Valves

Used for General Purpose Valves and Float Valves, the curve consists of a collection of points defining the headloss across the valve (y-axis) and flow rate in flow units (x-axis). A sample table and curve are provided below:

Float Valves

Many storage tanks and reservoirs are fitted with float valves (e.g., ball float valves) on the inlet pipe to control rate of flow and prevent overflow. These valves gradually close (increase the resistance of the inlet pipe) as the water level in the controlling tank rises. The headloss across the valve is modeled (via a curve) based on any user specified pairs of Headloss vs. Flow points. The valve is active if the water level in the controlling tank is below the lower control level or the water level is between the lower and upper levels after the valve opening. Likewise, the valve is closed if the water level in the controlling tank is at or above the upper control level or the water level is between the lower and upper after the valve closes. Float valves are not an EPANET valve type, but are essentially a GPV with a control statement on one of the pipes connected to the valve. Specify the Valve Type as Float Valve in the Type field of the Modeling Data section of the Model Explorer - Attribute Tab

Note: For Float Valves please do not enter any data to the Setting, or Minor Loss fields.

Vacuum Breaker Valves 

Vacuum breaker valves (VBV) are devices that allow air to enter at that location in the system when the pressure drops to atmospheric level. When the pressure drops to zero, the valve becomes active and will compute the correct flow rate required to maintain atmospheric condition. NOTE: VBVs may cause difficulties if locations downstream of the valve must receive water through the VBV type valve. VCBs are best used on dead ends to avoid creating a disconnected node warning when the valve closes. Specify the Valve Type as Vacuum Breaker Valve in the Type field of the Modeling Data section of the Model Explorer - Attribute Tab.

Required Fields:

Other Types of Valves (Assigned Directly to Pipe Element)

Check Valves

A valve located on a pipe that allows flow in one direction only. InfoWater Pro assumes that flow through pipes containing check valves is limited to the direction of the pipe (i.e., from the From-node U/S to the To-node D/S orientation). To add a check valve to a pipe, click on the pipe using the selection tool and from the Model Explorer - Attribute Tab, set Check Valve = Yes. All pipes containing Check Valves can be highlighted from the Domain Manager dialog box using the Special Query Element Source and selecting "Pipes" and "Check Valves".

Note: Pipes with check valves are not allowed to have any Initial Status or Controls defined on them. The pipe status will be decided only by the direction of flow and any additional control statements will cause an error.

Pipes with check valves should not be directly connected to pumps (except for Constant Power Type Pumps), valves, or tanks/reservoirs. All valves and pump types save for the Constant Power Pump have a check valve associated with them and hence do not allow reverse flow.

Flow Totalizers 

A meter located on a pipe that measures the cumulative bi-directional flow volume (ML or MG) through the pipe. If a flow totalizer is specified for a pipe, the Total Forward and Total Reverse fields on pipe reports will be populated. For pipes without flow totalizers, these fields will not be populated. InfoWater Pro will calculate and report the total flow volume in the forward and reverse direction (if flow reversal occurred) and the net flow volume.

To add a flow totalizer to a pipe, select the pipe and in the Model Explorer - Attribute Tab under the Modeling Data section, set Flow Totalizer = Yes.

Pipes containing flow totalizers are displayed in a similar fashion to those not containing flow totalizers. All pipes containing flow totalizers can be highlighted from the Domain Manager dialog box using the Special Query Element Source and selecting Pipes and Flow Totalizers.

PSV/PRV Combined

Note: To represent a static valve (e.g., gate valve), a minor loss can be assigned to a pipe. Valves represent a loss element that is used to throttle or control the flow through the element. To isolate or close an element to flow, use the Facility Manager to activate and inactivate elements.

Create a Valve

To create a Valve node:

Click on the InfoWater Pro Ribbon in the Edit Group using the    Insert Command dropbox

Select the Insert Valve icon   from the    Insert Command dropbox.

Note: When the Insert Valve command is the active command it will be highlighted in Blue as shown: .

Once the command is initiated, select the location of the new node by left mouse clicking anywhere on the map display. Suggest a new ID and/or a description on the  Valve Identification  dialog box and click OK to accept the ID and create the new Valve. The Valve should visually appear at the specified location. If the insert location is near an existing model pipe, the software will prompt you to insert the Valve into that pipe. If you wish to split the pipe, the  Valve Identification  dialog box for the new Valve and the new pipe will appear in a pop-up window.

Note: You can also use the Digitize Network icon   from the  Insert Command dropbox   to create a pipe and node network on the fly. Once digitized, you are able to add relevant modeling data in the Model Explorer - Attribute Tab window or via the DB Editor.

Edit a Valve

Graphic Selection - To select a Valve node for data edit do one of the following:

Choose the Select icon   from the Model Explorer - Attribute Tab window, and click on the specific Valve or select the InfoWater Pro Ribbon in the Edit Group using the    Select icon  .

If a Valve has been prior selected and is a part of the Browse history, it can be re-selected by choosing it from the Browse-History section of the Model Explorer - Attribute Tab window.

Data Edit - To edit the data related to a Valve, first select the Valve using the tools above. Once selected, edit Junction related data by adding/modifying the fields in the Model Explorer - Attribute Tab window. Additionally modifications may be done by editing the DB Tables that may be accessed from the InfoWater Pro Ribbon in the Edit Group using the    DB Editor  icon   .

Graphic Edit - To edit the node graphically do one of the following: From the InfoWater Pro Ribbon in the Edit Group using the    Edit Command dropbox  icon select the Move Node command   from the dropdown . Left click on the mouse and hold the left click down on the junction to select it. With the junction highlighted move the node to the desired position while keeping the left click mouse button depressed. Once in the desired location, release the left mouse button and the node location will be updated to the new location.

Note: When the Move Node command in the InfoWater Pro Ribbon in the Edit Group  Edit Command dropbox is the active command it will be highlighted in Blue as shown:  .
Note: If you have enabled Auto Length Calculation checkbox   from the InfoWater Pro Ribbon in the Project Group using the Preferences icon   and the Operations tab, all pipes connected to a node moved will not have their lengths automatically changed.

Edit Data for a Group of Valves

Group edits can be made by either creating a domain or by creating a selection.

Using the Domain Manager - Create a domain selecting the specific Valves that you want to edit. Refer to the section on Domain Manager for details on the domain creation process. Once the domain has been created, choose the InfoWater Pro Ribbon in the Edit Group using the    DB Editor icon . Depending on the data you want to edit choose the appropriate table type from among the different database tables. Choose as the Data Scope and click OK.

Using the User Selection - Select choose the InfoWater Pro Ribbon in the Edit Group using the    DB Editor  icon  . Depending on the data you want to edit choose the appropriate table type from among the different database tables. Choose as the Data Scope and choose the User Selection   command. This places the software in User Selection Mode. In InfoWater Pro, the Selected elements will be in a  cyan  color. Once all of the desired Valves are selected, right click and choose Enter to access the DB Tables for the selected Valves.

Once the specific tables have been opened with the desired scope, enter data one cell at a time or Block Edit data to make changes in bulk to multiple cells.

Note: Group Editing for certain specific features may also be done by choosing the Group Editing icon   or the Edit Domain icon  under the InfoWater Pro Ribbon in the Edit Group. Refer to the sections on Group Editing and Edit Domain to learn more.

Delete a Valve

To delete a Valve, select the Delete Node option   in the InfoWater Pro Ribbon in the Edit Group    Edit Command dropbox.  Select the node to be deleted and InfoWater Pro prompts you to confirm deletion (if the Delete Confirmation checkbox   is checked in the Operation Settings tab in the Preferences settings  .

The active selected Valve in the Model Explorer - Attribute Tab window may also be deleted by selecting the Delete icon   with the InfoWater Pro prompt to confirm element deletion.

Note: All pipes attached to the Node being deleted will also be deleted if the Auto Pipe Delete checkbox   is checked in the Operation Settings tab in the Preferences settings  . The Node and associated pipes are deleted and saved in the InfoWater Pro recycle bin and can be recalled from the database using the Model Explorer - Command Center Tab under Utilities - > Recall (Node or Pipe) command. However, if Auto Database Packing   is checked (Operation Settings tab in the Preferences settings  ), then any element deleted is permanently deleted from the database and cannot be recalled. Deleted elements can be recalled until the Pack and then Clean commands (found in the Model Explorer - Command Center Tab under Utilities    Database  menu list)are completed which removes deleted element ID's from the database.

Recall a Deleted Valve

To recall a deleted Valve, go to Model Explorer - Command Center Tab under Utilities - > Recall and select the Node command. In order to perform the recall, you must know the ID of the Valve that was deleted. You may choose the Show Deleted Node command to obtain a list of nodes deleted from the InfoWater Pro project but saved in the InfoWater Pro recycle bin. Deleted elements can be recalled until the Pack and then Clean commands (found in the Model Explorer - Command Center Tab under Utilities    Database  menu list) are completed which removes deleted element ID's from the database permanently.

Note:

Important Rules for Valves