Share
 
 

HVAC Systems

Learn about the assumptions used for each HVAC system during energy analysis.

To specify the type of HVAC system to use for energy analysis, use the Advanced Energy Settings dialog.

2-Pipe Fan Coil System, Chiller 5.96 COP, Boilers 84.5 eff

  • Water cooled centrifugal chiller (COP 5.96)
  • Open, atmospheric pressure cooling tower with variable speed fan and 5-degree Fahrenheit (2.8 degree Celsius) approach
  • Forward curved constant volume fan and premium efficiency motor
  • 0.25 inch of water gauge (62.3 pascals) static pressure Constant Volume duct system
  • Gas-fired hot water boiler with draft fan >2500 kBtuh, 84.5% combustion efficiency
  • Variable volume hot water pump
  • Hot water coil
  • Variable volume chilled water pump
  • Chilled water coil
  • Variable volume condenser water pump
  • Domestic hot water unit (0.575 Energy Factor)

4-Pipe Fan Coil System, Chiller 5.96 COP, Boilers 84.5 eff

  • Water cooled centrifugal chiller (COP 5.96)
  • Open, atmospheric pressure cooling tower with variable speed fan and 5-degree Fahrenheit (2.8-degree Celsius) approach
  • Forward curved constant volume fan and premium efficiency motor
  • 0.25 inch of water gauge (62.3 pascals) static pressure Constant Volume duct system
  • Gas-fired hot water boiler with draft fan >2500 kBtuh, 84.5% combustion efficiency
  • Variable volume hot water pump
  • Hot water coil
  • Variable volume chilled water pump
  • Chilled water coil
  • Variable volume condenser water pump
  • Domestic hot water unit (0.575 Energy Factor)

11 EER Packaged VAV, 84.5% boiler heating

  • Efficient 11 EER, >20-ton Packaged Variable Air Volume (VAV) Unit, Water Reheat, with Variable Speed Drive (VSD)
  • Forward curved fan with VSD and premium efficiency motor
  • 3.5 inch of water gauge (871.8 pascals) static pressure VAV duct system
  • Integrated differential dry-bulb temperature economizer
  • Gas-fired hot water boiler with draft fan >2500 kBtuh, 84.5% AFUE
  • Constant volume hot water pump
  • Hot water coil
  • Hot water reheat boxes
  • Domestic hot water unit (0.575 Energy Factor)

12 SEER/0.9 AFUE Split/Packaged Gas, 5-11 Ton

  • Efficient 12 SEER, 90% AFUE furnace split system with gas heat
  • Forward curved constant volume fan and premium efficiency motor
  • 2.0 inch of water gauge (498 pascals) static pressure Constant Volume duct system
  • Integrated differential dry-bulb temperature economizer
  • Domestic hot water unit (0.575 Energy Factor)

12 SEER/7.7 HSPF Split Packaged Heat Pump

  • Efficient 12 SEER/7.7 HSPF (Heating Seasonal Performance Factor) < 11.25-ton split/packaged heat pump system
  • Forward curved constant volume fan and premium efficiency motor
  • 2.0 inch of water gauge (498 pascals) static pressure Constant Volume duct system
  • Integrated differential dry-bulb temperature economizer
  • Domestic hot water unit (0.575 Energy Factor)

12 SEER/8.3 HSPF Packaged Terminal Heat Pump (PTHP)

  • 12 SEER/8.3 HSPF (Heating Seasonal Performance Factor) packaged terminal heat pump (PTHP)
  • Forward curved constant volume fan and premium efficiency motor
  • 0.25 inch of water gauge (62.3 pascals) static pressure Constant Volume duct system
  • Domestic hot water unit (0.575 Energy Factor)

Central VAV, Electric Resistance Heat, Chiller 5.96 COP

  • Water cooled centrifugal chiller (COP 5.96)
  • Open, atmospheric pressure cooling tower with variable speed fan and 5-degree Fahrenheit (2.8-degree Celsius) approach
  • Forward curved fan with Variable Speed Drive (VSD) and premium efficiency motor
  • 3.5 inch of water gauge (871.8 pascals) static pressure Variable Air Volume (VAV) duct system
  • Integrated differential dry-bulb temperature economizer
  • Resistance reheat boxes
  • Variable volume chilled water pump
  • Chilled water coil
  • Variable volume condenser water pump
  • Domestic hot water unit (0.575 Energy Factor)

Central VAV, HW Heat, Chiller 5.96 COP, Boilers 84.5 eff (default)

  • Water cooled centrifugal chiller (COP 5.96)
  • Open, atmospheric pressure cooling tower with variable speed fan and 5-degree Fahrenheit (2.8-degree Celsius) approach
  • Forward curved fan with Variable Speed Drive (VSD) and premium efficiency motor
  • 3.5 inch of water gauge (871.8 pascals) static pressure Variable Air Volume (VAV) duct system
  • Integrated differential dry-bulb temperature economizer
  • Gas-fired hot water boiler with draft fan >2500 kBtuh, 84.5% combustion efficiency
  • Variable volume hot water pump
  • Hot water coil
  • Hot water reheat boxes
  • Variable volume chilled water pump
  • Chilled water coil
  • Variable volume condenser water pump
  • Domestic hot water unit (0.575 Energy Factor)

Residential 14 SEER/0.9 AFUE Split/Packaged Gas <5.5 ton

  • Efficient 14 SEER/90% AFUE furnace <5.5-ton split/packaged system with gas heat
  • Residential constant volume cycling fan
  • 2.0 inch of water gauge (498 pascals) static pressure Constant Volume duct system
  • Domestic hot water unit (0.575 Energy Factor)

Residential 14 SEER/8.3 HSPF Split/Packaged Heat Pump

  • Efficient 14 SEER/8.3 HSPF (Heating Seasonal Performance Factor) <5.5-ton split/packaged heat pump system
  • Residential constant volume cycling fan
  • 2.0 inch of water gauge (498 pascals) static pressure Constant Volume duct system
  • Integrated differential dry-bulb temperature economizer
  • Domestic hot water unit (0.575 Energy Factor)

Residential 17 SEER/9.6 HSPF Split HP <5.5 ton

  • 17.4 SEER/9.6 HSPF <5.5-ton split/packaged air source heat pump, intermittent fan mode
  • Residential constant volume cycling fan
  • 2.0 inch of water gauge (498 pascals) static pressure Constant Volume duct system
  • Premium efficiency, on-demand tankless domestic hot water heater (0.85 Energy Factor)

Underflow Air Distribution

  • Packaged Variable Air Volume (PVAV) system with under floor air distribution
  • Forward curved fan with Variable Speed Drive (VSD) and premium efficiency motor
  • 3.5 inch of water gauge (871.8 pascals) static pressure VAV duct system
  • Gas-fired hot water boiler with draft fan >2500 kBtuh, 84.5% combustion efficiency
  • Integrated differential dry-bulb temperature economizer
  • Variable volume hot water pump
  • Hot water coil
  • Hot water reheat boxes
  • Improved efficiency domestic hot water heater (85% thermal efficiency)

Was this information helpful?