Learn about the default settings for space types in Revit.
You can change the default values for space type parameters. See Space Properties.
Active Storage
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Warehouse 7 am - 4 pm |
| People/100 sq. M. | 3.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.8 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Active Storage - Hospital/healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 3.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.9 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Air/Train/Bus - Baggage Area
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 100.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Airport Concourse
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 100 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.6 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Atrium - Each additional floor
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 33.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.2 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Atrium - First 3 floors
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 33.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.6 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Audience/Seating Area - Penitentiary
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 150 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.7 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Audience/Seating Area - Exercise Center
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Audience/Seating Area - Gymnasium
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Commercial 7 am - 6 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.4 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Audience/Seating Area - Sports Arena
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.4 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Audience/Seating Area - Convention Center
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 150 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.7 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Audience/Seating Area - Motion Picture Theatre
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 1.2 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Audience/Seating Area - Performing Arts Theatre
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 2.6 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Audience/Seating Area - Religious
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 120 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 1.7 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Audience/Seating Area - Police/Fire Station
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 50.0 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Audience/Seating Area - Courthouse
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 70.0 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Audience/Seating Area - Auditorium
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Bank Customer Area
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 30.0 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 1.49 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Banking Activity Area - Office
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 5.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.5 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.3 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Barber and Beauty Parlor
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 25.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1 |
| Power Load Density (W/sq. ft.) | 2 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Card File and Cataloguing - Library
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Classroom/Lecture/Training - Penitentiary
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 65.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Classroom/Lecture/Training
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | School 8 am - 9 pm |
| Power Schedule | School 7 am - 9 pm |
| People/100 sq. M. | 65.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.4 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Confinement Cells - Penitentiary
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 25.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Confinement Cells - Court House
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 25.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.9 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Conference/Meeting/Multipurpose
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 50.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Corridor/Transition
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.5 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Corridor/Transition - Manufacturing Facility
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 00.5 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Corridor w/Patient Waiting Exam - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Court Sports Area - Sports Area
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 30.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.3 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Courtroom - Court House
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 70.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.3 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Department Store Sales - Retail
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 15.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Detailed - Manufacturing Facility
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.1 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dining Area
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Restaurant Lunch and Dinner |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 70.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 275 |
| Lighting Load Density (W/sq. ft.) | 0.9 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Dining Area - Hotel
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Restaurant Lunch and Dinner |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 70.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 275 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Dining Area - Family Dining
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Restaurant Lunch and Dinner |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 70.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 275 |
| Lighting Load Density (W/sq. ft.) | 2.1 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Dining Area - Lounge/Leisure Dining
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Restaurant Lunch and Dinner |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 70.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 275 |
| Lighting Load Density (W/sq. ft.) | 1.4 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dining Area - Motel
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Hotel 24 hrs |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 70.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 275 |
| Lighting Load Density (W/sq. ft.) | 1.2 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dining Area - Transportation
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 100.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 275 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dining Area - Penitentiary
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 100.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 275 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dining Area - Civil Services
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Restaurant Lunch and Dinner |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 100.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 275 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dormitory Bedroom
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Home 24 hrs |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 155 |
| Lighting Load Density (W/sq. ft.) | 1.11 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Dormitory Study Hall
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 155 |
| Lighting Load Density (W/sq. ft.) | 1.11 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Dressing/Locker/Fitting Room - Gymnasium
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.6 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dressing/Locker/Fitting Room - Court House
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Lighting Schedule | Office Lighting 6 am - 11 pm |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dressing/Locker/Fitting Room - Performing Arts Theatre
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dressing/Locker/Fitting Room - Auditorium
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Dressing/Locker/Fitting Room - Exercise Center
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Electrical/Mechanical
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Restaurant Lunch and Dinner |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 3.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.5 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Elevator Lobbies
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 0.2 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Emergency - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.7 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Equipment Room - Manufacturing Facility
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 3.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.2 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Exam/Treatment - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.5 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Exercise Area - Exercise Center
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 30.0 |
| People Sensible Heat Gain (Btu/hr) | 710 |
| People Latent Heat Gain (Btu/hr) | 1090 |
| Lighting Load Density (W/sq. ft.) | 0.93 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Exercise Area - Gymnasium
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 30.0 |
| People Sensible Heat Gain (Btu/hr) | 710 |
| People Latent Heat Gain (Btu/hr) | 1090 |
| Lighting Load Density (W/sq. ft.) | 0.9 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Exhibit Space - Convention Center
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 50.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Fellowship Hall - Religious Buildings
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 120.0 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.9 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Fine Material - Warehouse
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Warehouse 7 am - 4 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.4 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Fine Merchandise - Sales Area Retail
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 15.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Fire Station Engine Room - Police Fire Station
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.8 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Food Preparation
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Restaurant Lunch and Dinner |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.2 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Garage Service/Repair - Automotive Facility
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.7 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
General High Bay - Manufacturing Facility
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.7 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
General Low Bay - Manufacturing Facility
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.2 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
General Exhibition - Museum
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 40.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Hospital - Nursery - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.6 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Hospital - Medical Supplies - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 3.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.4 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Hospital/Radiology- Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.4 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Hotel/Conference Center - Conference/Meeting
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Hotel 24 hrs |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 50.0 |
| People Sensible Heat Gain (Btu/hr) | 225 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Inactive Storage
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Warehouse 7 am - 4 pm |
| People/100 sq. M. | 3.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.3 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Judges Chambers - Court House
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 50.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Laboratory - Office
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 5.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.4 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Laundry - Ironing and Sorting
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 475 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Laundry - Washing - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 275 |
| People Latent Heat Gain (Btu/hr) | 475 |
| Lighting Load Density (W/sq. ft.) | 0.6 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Library - Audio Visual - Library - Audio Visual
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 25.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Living Quarters - Dormitory
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Hotel 24 hrs |
| Power Schedule | Residential Lighting All Day |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 155 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Living Quarters - Motel
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Hotel 24 hrs |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 155 |
| Lighting Load Density (W/sq. ft.) | 1.11 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Living Quarters - Hotel
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Hotel 24 hrs |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 155 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Lobby
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 150.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 155 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Lobby - Religious Building
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Lobby - Motion Picture Theatre
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Lobby - Auditorium
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Lobby - Performing Arts Theatre
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 3.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Lobby - Post Office
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 150.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.3 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Lobby - Hotel
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Hotel 24 hrs |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 150.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Lounge or Recreation
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 30.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.21 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Mail Concourse Sales Area - Retail
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 40.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.7 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Mass Merchandising Sales Area - Retail
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Warehouse 7 am - 4 pm |
| People/100 sq. M. | 15.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.11 |
| Power Load Density (W/sq. ft.) | 0.1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Medium/Bulky Material - Warehouse
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Warehouse 7 am - 4 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.9 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Merchandising Sales Area - Retail
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 15.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Museum and Gallery - Storage
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 5.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.84 |
| Power Load Density (W/sq. ft.) | 0.2 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Nurse Station - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.3 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Office - Enclosed
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 5.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.3 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Office - Open Plan
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 5.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.3 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Office - Common Activity Areas - Inactive Storage
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Warehouse 7 am - 4 pm |
| People/100 sq. M. | 3.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.28 |
| Power Load Density (W/sq. ft.) | 0.2 |
| Electrical Equipment Radiant Percentage | 0.3 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Operating Room - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.2 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Other Televised Playing Area - Sports Arena
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 150.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.4 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Parking Area - Attendant Only - Parking Garage
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 5.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.19 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Parking Area - Pedestrian - Parking Garage
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 5.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.2 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Patient Room - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.7 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Personal Services Sales Area - Retail
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 15.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Pharmacy - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.2 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Physical Therapy - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.9 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Playing Area Gymnasium
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 30.0 |
| People Sensible Heat Gain (Btu/hr) | 710 |
| People Latent Heat Gain (Btu/hr) | 1090 |
| Lighting Load Density (W/sq. ft.) | 1.4 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Plenum
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Cooling/Heating Off 24 hrs |
| Power Schedule | Cooling/Heating Off 24 hrs |
| People/100 sq. M. | 00 |
| People Sensible Heat Gain (Btu/hr) | 0 |
| People Latent Heat Gain (Btu/hr) | 0 |
| Lighting Load Density (W/sq. ft.) | 0 |
| Power Load Density (W/sq. ft.) | 0 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0 |
| Carpet (Y/N) | N |
Police Station Laboratory - Police/Fire Stations
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 25.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.39 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Public and Staff Lounge - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 25.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.84 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Reading Area - Library
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.2 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Reception/Waiting - Transportation
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 100.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Reception/Waiting - Motel
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Hotel 24 hrs |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 30.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Reception/Waiting - Hotel
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Hotel 24 hrs |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 30.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.1 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Recovery - Hospital/Healthcare
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.8 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Restoration - Museum
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 40.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.7 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Restrooms
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.9 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Ring Sports Area - Sports Arena
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 70.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.7 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Sleeping Quarters - Police/Fire Station
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 105 |
| Lighting Load Density (W/sq. ft.) | 0.3 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Sorting Area - Post Office
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 5.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.2 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Specialty Store Sales Area - Retail
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 15.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.14 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Stacks - Library
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.7 |
| Power Load Density (W/sq. ft.) | 1.5 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Stairs - Inactive
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.56 |
| Power Load Density (W/sq. ft.) | 0.2 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Stairway
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Common Office 8 am - 5 pm |
| Power Schedule | Office Lighting 6 am - 11 pm |
| People/100 sq. M. | 10.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 0.6 |
| Power Load Density (W/sq. ft.) | 0.3 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Supermarket Sales Area - Retail
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Retail Facility 7 am - 8 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 8.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.1 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Terminal - Ticket Counter - Transportation
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Healthcare Facility 8 am - 9 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 100.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.5 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |
Workshop - Workshop
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Warehouse 7 am - 4 pm |
| Power Schedule | Warehouse 7 am - 4 pm |
| People/100 sq. M. | 20.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 1.9 |
| Power Load Density (W/sq. ft.) | 1 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | N |
Worship - Pulpit Choir - Religious
| Parameter | Default Value |
|---|---|
| Occupancy Schedule | Large Assembly Hall 8 am - 10 pm |
| Power Schedule | Retail Lighting 7 am - 8 pm |
| People/100 sq. M. | 120.0 |
| People Sensible Heat Gain (Btu/hr) | 250 |
| People Latent Heat Gain (Btu/hr) | 200 |
| Lighting Load Density (W/sq. ft.) | 2.4 |
| Power Load Density (W/sq. ft.) | 0.54 |
| Electrical Equipment Radiant Percentage | 0.5 |
| Infiltration Flow (CFM/sq. ft.) | 0.038 |
| Carpet (Y/N) | Y |