Unit Ventilator

Unit ventilators provide a controlled means of introducing conditioned outdoor air during the heating season.

Required Objects

The unit ventilator must have the following property.
  • It must be attached to a conditioned zone.

Design Assumptions

If the Draw Ventilation property is selected, the following will occur.

  • The unit will provide the design outdoor air flow.
  • The fan will run constantly during occupied hours.

If the Draw Ventilation property is not selected, the following will occur.

  • The unit will not provide any ventilation.
  • The fan will cycle on and off to meet conditioning needs.
Property Value Notes
System air flow Constant
Cooling supply air temperature 12.78°C
Heating supply air temperature 40°C

Cooling Coil

The cooling coil has the following assumptions.

  • The DX coil is single-speed with aa rated COP of 3.0.
  • The sensible-to-latent heat ratio is auto-sized to meet the system needs during sizing.
  • The chilled water coil has the following assumptions.
Property Value Notes
Coil entering air temperature N/A Determined by the design day.
Coil leaving air temperature ~11.11°C Calculated from the air system supply air temperature minus fan heat generated (typically about 1.5°C - 2°C).
Chilled water design inlet temperature N/A Set by the chilled water loop if chilled water coil is used in the system.
Chilled water design outlet temperature N/A Set by the chilled water loop if chilled water coil is used in the system.

Heating Coil

The heating coil has the following assumptions.

  • The electric resistence heating coil is 100% efficient.
  • The furnace heating coil is 80% efficient.
  • The hot water coil has the following properties.
Property Value Notes
Coil leaving air temperature 40°C
Hot water design inlet temperature N/A Set by the hot water loop.
Hot water design outlet temperature N/A Set by the hot water loop.

Supply Fan

The supply fan has the following properties:

Property Value Notes
Pressure rise 250 Pa
Total efficiency 70%
Motor efficiency 94%