Four Pipe Fan Coil

Fan coils provide conditioned air to an area by recirculating air through the coils. A four-pipe fan coil unit consists of a fan, air filter, chilled water cooling coil, and hot water heating coil.

Required Objects

The four pipe fan coil must have the following properties.
  • It must be connected to a hot water loop.
  • It must be connected to a chilled water loop.
  • It must be attached to a conditioned zone.

Design Assumptions

If the Draw Ventilation property is selected, the following will occur.

  • The unit will provide the design outdoor air flow.
  • The fan will run constantly during occupied hours.

If the Draw Ventilation property is not selected, the following will occur.

  • The unit will not provide any ventilation.
  • The fan will cycle on and off to meet conditioning needs.
Property Value Notes
System air flow Constant
Cooling supply air temperature 12.78°C
Heating supply air temperature 40°C

Cooling Coil

The cooling coil has the following assumptions.

Property Value Notes
Design coil leaving air temperature 12.78°C
Chilled water design inlet temperature N/A Set by the chilled water loop.
Chilled water design outlet temperature N/A Set by the chilled water loop.

Heating Coil

The heating coil has the following assumptions.

Property Value Notes
Coil leaving air temperature 40°C
Hot water design inlet temperature N/A Set by the hot water loop.
Hot water design outlet temperature N/A Set by the hot water loop.

Supply Fan

The supply fan has the following assumptions.

Property Value Notes
Pressure rise 250 Pa
Total efficiency 70%
Motor efficiency 94%